JSN L2691<br />

Name Hematocrit Accessory, Automatic<br />

Logistical Category (LOGCAT) Fund Source Weights and Measures (Typical Only)<br />

Army C | Government Furnished, Government Installed<br />

Navy C | Government Furnished, Government Installed<br />

USAF C | Government Furnished, Government Installed<br />

VA C | Government Furnished, Government Installed<br />

IHS C | Government Furnished, Government Installed<br />

Utilities<br />

NSN 6630<br />

NOTE: Values shown are based on standard typicals used for programming purposes. <strong>The</strong> contractor remains responsible to<br />

develop and coordinate the design / construction in accordance with actual equipment selection.<br />

Utility1: Plumbing . |<br />

Volts1 120<br />

Utility2: Electrical A | 120 volt, conventional outlet<br />

Utility3: Med Gas . |<br />

Utility4: Misc Gas . |<br />

Utility5: Non-Med Gas . |<br />

Utility6: Misc . |<br />

Phase1 1<br />

Phase2 1<br />

Amps1 8<br />

Amps2 0<br />

Weight (lbs) 124 Weight (kgs) 57<br />

Height (in) 20 Height (cen) 51<br />

Width (in) 26 Width (cen) 66<br />

Depth (in) 21 Depth (cen) 53<br />

Volts2 12<br />

Hertz 60<br />

Hertz Dep 0<br />

Hertz Switch -1<br />

BTU / Hour 1571<br />

Watts1 960<br />

Watts2 0<br />

Description<br />

Unit of Issue EA<br />

Group Laboratory <strong>Equipment</strong><br />

Automatic hematocrit accessory. This accessory calculates the volume of packed cells from total cell count and MCV and provides a<br />

reproducibility to plus or minus 1% for use with the counter. <strong>The</strong> hematocrit accessory is integrated into the total instrument package.<br />

JSN L3160<br />

Name Washer, Labware, Steam<br />

Logistical Category (LOGCAT) Fund Source Weights and Measures (Typical Only)<br />

Army A | Contractor Furnished, Contractor Installed<br />

Navy A | Contractor Furnished, Contractor Installed<br />

USAF A | Contractor Furnished, Contractor Installed<br />

VA A | Contractor Furnished, Contractor Installed<br />

IHS A | Contractor Furnished, Contractor Installed<br />

Utilities<br />

NSN 6640<br />

NOTE: Values shown are based on standard typicals used for programming purposes. <strong>The</strong> contractor remains responsible to<br />

develop and coordinate the design / construction in accordance with actual equipment selection.<br />

Utility1: Plumbing F | Cold, hot and treated water and drain<br />

Volts1 208<br />

Utility2: Electrical G | 208/220 volt, 3 phase<br />

Utility3: Med Gas . |<br />

Utility4: Misc Gas A | Steam<br />

Utility5: Non-Med Gas . |<br />

Utility6: Misc . |<br />

Phase1 3<br />

Phase2 0<br />

Amps1 20<br />

Amps2 0<br />

Weight (lbs) 1257 Weight (kgs) 571<br />

Height (in) 95 Height (cen) 241<br />

Width (in) 46 Width (cen) 117<br />

Depth (in) 50 Depth (cen) 127<br />

Volts2 0<br />

Hertz 60<br />

Hertz Dep -1<br />

Hertz Switch 0<br />

BTU / Hour 8500<br />

Watts1 7206<br />

Watts2 0<br />

Description<br />

Unit of Issue EA<br />

Group Laboratory <strong>Equipment</strong><br />

Single door, steam operated, cabinet mounted, metalware and glassware washer, approximately 80" H x 39" W x 31" D. Used in hospitals<br />

to wash glassware and metal utensils. Optional electric heating may be available (add 40 Amps to power requirements).<br />