JSN M4840<br />

Name ENT Unit, w/Air, Electric Power, Suction, Pressure<br />

Logistical Category (LOGCAT) Fund Source Weights and Measures (Typical Only)<br />

Army C | Government Furnished, Government Installed<br />

Navy C | Government Furnished, Government Installed<br />

USAF C | Government Furnished, Government Installed<br />

VA C | Government Furnished, Government Installed<br />

IHS C | Government Furnished, Government Installed<br />

Utilities<br />

NSN 6530<br />

NOTE: Values shown are based on standard typicals used for programming purposes. <strong>The</strong> contractor remains responsible to<br />

develop and coordinate the design / construction in accordance with actual equipment selection.<br />

Utility1: Plumbing . |<br />

Volts1 120<br />

Utility2: Electrical A | 120 volt, conventional outlet<br />

Utility3: Med Gas H | Vacuum and HP air (85 PSIG) minimum<br />

Utility4: Misc Gas . |<br />

Utility5: Non-Med Gas . |<br />

Utility6: Misc . |<br />

Phase1 1<br />

Phase2 0<br />

Amps1 6<br />

Amps2 0<br />

Weight (lbs) 165 Weight (kgs) 75<br />

Height (in) 45 Height (cen) 114<br />

Width (in) 35 Width (cen) 89<br />

Depth (in) 25 Depth (cen) 64<br />

Volts2 0<br />

Hertz 60<br />

Hertz Dep 0<br />

Hertz Switch 0<br />

BTU / Hour 0<br />

Watts1 720<br />

Watts2 0<br />

Description<br />

Unit of Issue EA<br />

Group Miscellaneous<br />

Mobile ENT unit. Unit has air and electrical panels and integral suction and pressure system. Unit houses a control panel with functions<br />

selector, pressure regulator, pressure gauge and electrical outlets. It is equipped with foot-controlled vacuum and pressure plus a storage<br />

area.<br />

JSN M4850<br />

Name Flushing Unit, Renal Dialysis Cartridge<br />

Logistical Category (LOGCAT) Fund Source Weights and Measures (Typical Only)<br />

Army C | Government Furnished, Government Installed<br />

Navy C | Government Furnished, Government Installed<br />

USAF C | Government Furnished, Government Installed<br />

VA C | Government Furnished, Government Installed<br />

IHS C | Government Furnished, Government Installed<br />

Utilities<br />

NSN 6530<br />

NOTE: Values shown are based on standard typicals used for programming purposes. <strong>The</strong> contractor remains responsible to<br />

develop and coordinate the design / construction in accordance with actual equipment selection.<br />

Utility1: Plumbing E | Treated water and drain<br />

Volts1 120<br />

Utility2: Electrical A | 120 volt, conventional outlet<br />

Utility3: Med Gas . |<br />

Utility4: Misc Gas . |<br />

Utility5: Non-Med Gas . |<br />

Utility6: Misc E | Vent to atmosphere<br />

Phase1 1<br />

Phase2 0<br />

Amps1 15<br />

Amps2 0<br />

Weight (lbs) 150 Weight (kgs) 68<br />

Height (in) 25 Height (cen) 64<br />

Width (in) 30 Width (cen) 76<br />

Depth (in) 25 Depth (cen) 64<br />

Volts2 0<br />

Hertz 60<br />

Hertz Dep -1<br />

Hertz Switch 0<br />

BTU / Hour 0<br />

Watts1 1800<br />

Watts2 0<br />

Description<br />

Unit of Issue EA<br />

Group Miscellaneous<br />

Used for removing disinfectant or storage solution from renal dialysis cartridges prior to patient use. <strong>The</strong> manufacturer recommends a<br />

dedicated 20 amp ground fault interrupt protected circuit for this equipment. See manufacturer's pre-installation checklist for ventilation<br />

requirements.<br />

Thursday, April 21, 2011 <strong>MIL</strong>-<strong>STD</strong> <strong>1691</strong> | PPMD<br />