PART 3 - EXECUTION<br />

3.1 Examination: Examine areas and conditions under which potable water system's materials and<br />

products are to be installed. Do not proceed with work until unsatisfactory conditions have been<br />

corrected in manner acceptable to Installer.<br />

3.2 EARTHWORK<br />

A. Excavation trenching, and backfilling are specified in Division 2 Section "Earth Moving."<br />

3.3 INSTALLATION<br />

A. Identification: During back-filling/top-soiling of underground fire water piping systems, install<br />

continuous underground-type plastic line marker, located directly over buried line at 6" to 8"<br />

below finished grade. If pvc pipe is used, install a tracer wire along the top of the pipe, secured<br />

with tape, and extending to fire hydrants and valves.<br />

B. Pipe and pipe fittings:<br />

1. Pipe: Install in accordance with AWWA C600 "Standard for Installation of Ductile-Iron<br />

Water Mains and Their Appurtenances".<br />

2. Depth of Cover: Provide minimum depth of cover over underground piping in accordance<br />

with NFPA 24, Figure A-8-11 "Recommended Depth of Cover Above Top of Underground<br />

Yard Mains" or 60" below finish grade, whichever is greater.<br />

C. Piping Specialties:<br />

1. Pipe Line Strainers: Install as indicated, with valved blowoff piped to drain.<br />

D. Meters: Install as indicated with shutoff valve on either side of meter and valved bypass full line<br />

size.<br />

E. Valves: Provide post indicator for control valves.<br />

1. Shutoff Valves: Install shutoff valve ahead of each hydrant.<br />

F. Hydrants: Install fire hydrants in accordance with AWWA M17 "Installation, Operation, and<br />

Maintenance of Fire Hydrants".<br />

1. Location: Install fire hydrants minimum of 40'-0" from building outside wall, as indicated,<br />

or if not shown.<br />

2. Face hydrants towards drive.<br />

3. Place hydrants so that base of hydrant is even to 6-inches above adjacent top back of<br />

curb.<br />

3.4 PIPING APPLICATIONS<br />

A. Pipe:<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION MARCH 2, 2009<br />

WATER UTILITY PIPING 02008 - 5