diameter shall be Class 54, minimum; pipe sizes 20-inch nominal diameter shall be<br />

Class 55, minimum; pipe sizes 24-inch in nominal diameter shall be Class 56, minimum.<br />

Grooved-end pipe shall be supported in accordance with manufacturer's<br />

recommendations. In addition, at least one support shall be used between any two<br />

couplings.<br />

3. The Contractor shall submit a listing of services and locations where he proposes to<br />

use grooved-end pipe prior to start of installation of any grooved-end piping. This listing<br />

shall be subject to the Engineer's acceptance, and acceptance in writing by the Engineer<br />

will be required prior to the delivery of any grooved piping materials to the site of the<br />

Work.<br />

4. The Contractor shall submit for review complete information showing fittings, gaskets,<br />

mechanical pipe couplings, grooving of pipe and pipe lining or coating prior to installation<br />

of any pipe. All materials proposed for use are subject to Engineer's acceptance.<br />

5. Mechanical pipe couplings and grooved-end pipe shall be installed in accordance with<br />

the coupling manufacturer's representative's recommendations.<br />

PART 10 GROOVED-END DUCTILE IRON PIPE<br />

A. COUPLINGS AND FITTINGS<br />

PART 11 JOINTS<br />

1. Grooved-end ductile iron pipe shall be joined by mechanical pipe couplings.<br />

Mechanical couplings shall be self-centering and shall engage and lock in place the<br />

grooved pipe and pipe fitting ends in a positive watertight couple. Couplings shall be<br />

fabricated in two or more parts of malleable iron in accordance with ASTM A 47,<br />

Grade 32510. Couplings shall be the flexible grooved type for radius grooved pipe.<br />

2. Coupling assembly shall be securely held together by two or more steel bolts and nuts<br />

of heat-treated carbon steel. Nuts and bolts shall be in accordance with ASTM A 183<br />

and ASTM A 194, Grade 2.<br />

3. Couplings shall hold in place a composition water-sealing gasket designed so that<br />

internal water pressure serves to increase the seal's water tightness. Sealing gaskets<br />

shall be chlorinated butyl in accordance with ASTM D 2000, Grade No. 3BA6l5Al4Bl3<br />

with special heat-resistance test of 16 hours at 350 degrees F and maximum elongation<br />

change of minus 30 percent.<br />

4. All pipe fittings used in connection with mechanical pipe couplings shall be radius<br />

grooved for grooved-end ductile iron pipe. Radius grooved cast iron fittings shall conform<br />

to the requirements of ANSI B 16.1. The outside surface of pipe between the groove and<br />

pipe end must be smooth and free from deep pits or swells and shall provide a leak tight<br />

surface for the gasket.<br />

A. Where so indicated or specified, joints shall be made with flexible couplings or with mechanical<br />

couplings for grooved or shouldered end pipe. Unless otherwise noted, joints that are not buried<br />

in the ground shall be flanged joints. All other joints shall be mechanical joints, or push-on joints.<br />

Mechanical joint, or push-on joint pipelines shall have flanges where necessary for valves and<br />

clean out connections.<br />

PART 12 FLANGED JOINTS<br />

A. Flanges may be cast integrally with the pipe, in which case they shall conform to ANSI B 16.1<br />

as to diameter, thickness, drilling, and other characteristics or they may be screwed on the<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION 02630 - 5<br />

PIPING, VALVE, GATES AND SPECIALTIES MARCH 2, 2009