B. Review and coordinate security system layout and wiring with Jordan School District<br />

Maintenance Department and get approval prior to rough-in.<br />

C. Coordinate all equipment locations and mounting details with other trades and suppliers.<br />

D. Mount security devices a minimum of 3 feet from heat or air movement sources<br />

E. GROUNDING: Provide grounding connections sufficiently tight to assure permanent and<br />

effective ground.<br />

F. TESTING: Upon completion of installation of system and after energized, demonstrate<br />

system compliance with intent.<br />

G. WIRING: Install all wiring in conduit raceway. Wire all components of the system as shown<br />

and in accordance with factory recommendations. All devices shall be wired through POPIT<br />

modules to a data loop which is tied to the control communicator. All final connections shall<br />

be made by a qualified technician familiar with the school district procedures and the<br />

manufacturer's equipment. Label each junction box throughout system, ‘Security’, indicate<br />

zone number, and paint cover of junction boxes orange (Kwal Howells Orange Fiesta<br />

AC107Y).<br />

H. In addition to those shown on drawings, provide 20 popits, 20 door contacts, 10 wide infrared<br />

detectors, 10 narrow infrared detectors, 10 360° infrared detectors, and 5 card readers as<br />

directed by Architect/ Engineer. Provide 100’ of conduit with 2 pair #18 twisted for each<br />

device and connect into loop as directed. Provide 1000’ of conduit with Belden #638AFS<br />

cable for each reader. Credit back all unused material and labor to the Owner.<br />

I. ZONING: Each location shall be provided with a D8127T POPIT module which has been<br />

assigned a discreet address. Each detector, door switch, sensing device shall be considered<br />

a location. Multiple doors at a common entry shall be considered one location.<br />

J. LABELING: Label all devices with their appropriate address with 30 point KROY labels.<br />

K. WARRANTY: Provide warranty complying with Division 16001.<br />

L. Directed by the Engineer/Architect.<br />

3.2 AS BUILT DRAWINGS:<br />

A. A complete set of CAD “AS-BUILT” Drawings showing installed wiring, color coding, specific<br />

interconnections between all equipment, and internal wiring of the equipment shall be<br />

delivered to the owner upon completion of the system.<br />

B. A building map (2 copies)shall be supplied to the owner indicating the exact location of all<br />

devices along with the addresses of the individual devices. Install building security map<br />

adjacent to the security control panel. Provide high quality plastic sign (map holder) with two<br />

layers. The back layer shall be painted black. The front layer shall be a clear center for<br />

viewing the CAD security drawing. Edges of the sign shall be colored to match the building<br />

interior. The building map shall indicate the various by the use of different colors (minimum<br />

of five colors).<br />

C. The disk containing the files shall be supplied to the owner. These disks shall include all<br />

information required to allow the district to change the security program themselves. These<br />

computer disks shall contain a minimum of the following:<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

SECURITY INTRUSION DETECTION AND ACCESS CONTROL SYSTEMS 16781-4