1.3 SUBMITTALS:<br />

Neutral to Ground 40,000 amps<br />

Per Phase: 80,000 amps<br />

A. Submit complete and descriptive shop drawings in accordance with the General Conditions,<br />

Division 1, and Section 16050.<br />

B. Submit all related TVSS <strong>Specification</strong>s and drawing information requested in this document<br />

and U.L. 1449 Second Edition surge suppression ratings for the TVSS. In order for a TVSS<br />

system to be considered, all responses to information requested in this specification must be<br />

provided in writing. If a manufacturer cannot comply with any portion of this specification, this<br />

must be stated in the reply and the reason for non-compliance shall be provided.<br />

C. Submit operation and maintenance data in accordance with the General Conditions, Division<br />

1, and Section 16050.<br />

PART 2 - PRODUCTS<br />

2.1 ACCEPTABLE MANUFACTURERS:<br />

A. Provide products of one of the following manufacturers:<br />

1. Liebert<br />

2. LEA International<br />

3. Current Technologies<br />

4. Advanced Protection Technologies<br />

5. Intermatic Inc.<br />

6. GE Power Quality<br />

7. Cutler Hammer Clipper<br />

8. Square D<br />

9. Siemens<br />

10. EFI<br />

B. Requests for substitution of other products will be considered if submitted in accordance with<br />

the General Conditions, Division 1 and section 16050.<br />

2.2 TVSS EQUIPMENT:<br />

A. The TVSS shall be suitable for application in category C environments as described in<br />

ANSI/IEEE C62.41. The TVSS shall be of parallel design and provide protection from Line to<br />

Ground, Line to Line, Line to Neutral, and Neutral to Ground.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

TRANSIENT VOLTAGE SURGE SUPPRESSORS 16478-2