Louvers shall be Airolite, Air Balance, Air Guide, American Warming or Dowco.<br />

ROOF HOODS:<br />

Furnish and install complete the roof hoods shown on plans and specified in the Equipment Schedule. All<br />

units shall be rigid aluminum construction, with vertical seams continuously welded. Hoods shall be<br />

stressed and sloped for drainage, and shall be complete with birdscreen, reinforced self-flashing insulated<br />

base, and<br />

all accessories required for a complete installation. Hoods shall be designed and fabricated to withstand<br />

wind gusts of 150 MPH without physical damage.<br />

Roof hoods shall be Penn "Airette", Airolite, or Cook.<br />

EXHAUST OR VENTILATION FANS:<br />

Roof-Mounted Type:<br />

Furnish and install complete the low profile roof-mounted exhaust fans of the size and capacity shown on<br />

the drawings.<br />

Roof-mounted fans shall be of the centrifugal type with spun aluminum hood. All parts exposed to weather<br />

and all fastenings shall be either aluminum or stainless steel. All fans to be equipped with permanently<br />

lubricated 2-speed (where specified) ball bearing motors located in separate compartment out of the air<br />

stream. Fan shall have adjustable V-belt drive, self-flashing insulated curb, backdraft dampers, birdscreen,<br />

disconnect switch, and shall be complete with all necessary fittings and transition pieces for a complete<br />

installation. All units shall bear the AMCA certified performance seal.<br />

Fans shall be Twin City, Cook, Penn, or Jenn-Air.<br />

Roof Mounted Ventilation Type:<br />

Furnish and install complete the roof mounted ventilation fan shown and specified on the drawings.<br />

Fan shall be a hooded, low profile, filtered, roof mounted, belt driven, propeller supply fan<br />

The fan shall be of bolted and welded construction. The motor, bearings, and drives shall be mounted on a<br />

welded tubular steel power assembly. The power assembly shall be rigidly secured to the fan housing. The<br />

steel fan housing shall include a minimum 14 gauge base with integral spun venture and continuously<br />

welded curb cap corners. The fan shall be enclosed with a minimum 18 gauge galvanized steel hood bolted<br />

to the fan housing. The hood shall have a removable top cap to allow unobstructed access to the motor and<br />

power assembly without removing entire hood. Filters shall be washable expanded aluminum media with 2”<br />

formed aluminum frame.<br />

All steel fan components shall be coated with a baked polyester powder coating. Paint must exceed 1,000<br />