SECTION 16530 – LIGHTING CONTROL<br />

PART 1 - GENERAL<br />

1.1 WORK INCLUDED:<br />

A. Provide manual and/or automatic control for all lighting fixtures shown. Exit and emergency<br />

pathway lighting shall be controlled at branch circuit panel only.<br />

B. Provide one low voltage relay for each 20 amp 120 volt 1p or 208 volt 2 pole lighting branch<br />

circuit except for exit and pathway lighting circuits. Mount relays in cabinets and locate relay<br />

cabinets adjacent to the lighting branch circuit panels.<br />

1.2 RELATED WORK:<br />

A. Section 16050: Basic Electrical Materials and Methods<br />

B. Section 16110: Raceways<br />

C. Section 16120: Wires and Cables<br />

D. Section 16141: Switches and Receptacles<br />

E. Division 15: Energy management system. All low voltage control wiring is included in<br />

Division 15 control section except as specified.<br />

1.3 SUBMITTALS:<br />

A. Submit catalog data of relays and cabinets. All equipment must be UL listed.<br />

PART 2 - PRODUCTS<br />

2.1 ACCEPTABLE MANUFACTURERS:<br />

A. Relays and cabinets: All components must be of the same manufacture; acceptable<br />

manufacturers are: Sierra, General Electric, Pass and Seymour or approved substitute.<br />

B. Relays: Electrically operated, mechanically held; 20 amp, 208 volt or 120 volt contact rating.<br />

Momentary switching voltage: 24 VAC. GE No. RR-7. Provide quantity of relays as shown on<br />

the drawings.<br />

C. Cabinet: Flush mounted metal enclosure with screw on cover, rust proofed and painted to<br />

match branch circuit panels; barrier between line and low voltage section with knockouts for<br />

mounting up to 12 relays minimum; barrier to be vibration isolated from box. Each box to be<br />

assembled and provided with low voltage, line voltage terminal strips and relays only; all<br />

terminal strips shall be numbered.<br />

PART 3 - EXECUTION<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

LIGHTING CONTROL 16530-1