10.04.2013 Views

Complete Compiled Specification.pdf - Peck Ormsby Construction

Complete Compiled Specification.pdf - Peck Ormsby Construction

Complete Compiled Specification.pdf - Peck Ormsby Construction

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

1.2 REFERENCES:<br />

b. Providing 120V wiring and outlets.<br />

c. Providing servers, computers, and other active devices except as described in<br />

subsection 1A.<br />

d. Configuration of network switches provided by contractor to be completed by<br />

Alpine School District IT Department. Deliver device to the department for this<br />

process.<br />

e. Purchase and installation of network components, and phone system.<br />

f. Cable pathways – conduit, cable basket (with exception of MDF and IDF’s), etc<br />

to be installed by division 16000 contractor. See Part 3 Execution for<br />

requirements. Cable tray is not to be any less than 12 inches wide and 4 inches<br />

high through main corridor pathways.<br />

A. Test and install telecommunications cabling network per manufacturer's requirements and in<br />

accordance with NFPA-70 (National Electrical Code®), state codes, local codes, requirements<br />

of authorities having jurisdiction, and particularly the following standards.<br />

**Also reference Part 3: Execution for specific detail on conduit paths, conduit sizing<br />

and District expectations for installation.<br />

ANSI/TIA/EIA Standards<br />

1. ANSI/TIA/EIA-568-B.1 - Commercial Building Telecommunications Cabling Part: 1.<br />

(Except where specified as exception) general requirements<br />

2. ANSI/TIA/EIA-568-B.2 - Commercial Building Telecommunications cabling standard<br />

Part 2: Balanced twisted pair cabling components<br />

3. ANSI/TIA/EIA-568-B.3 - Optical fiber cabling component standards.<br />

4. ANSI/TIA/EIA-569-A - Commercial Building Standard for Telecommunications<br />

Pathways and Spaces.<br />

5. ANSI/TIA/EIA-606 - The Administration Standard for the Telecommunications<br />

Infrastructure of Commercial Buildings.<br />

6. ANSI/TIA/EIA-607 - Commercial Building Grounding and Bonding Requirements for<br />

Telecommunications.<br />

B. Install cabling in accordance with the most recent edition of BICSI® publications:<br />

1.3 SYSTEM DESCRIPTION<br />

BICSI - Telecommunications Distribution Methods Manual.<br />

BICSI - Cabling Installation Manual.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

TELEPHONE AND DATA DISTRIBUTION 17000-2