SECTION 02668 - FIRE WATER SYSTEM<br />

PART 1 - GENERAL<br />

1.1 SUMMARY<br />

A. Section includes fire water systems.<br />

B. Related Sections:<br />

1. Refer to Division-2 section 02004 "Excavation Support Protections" for excavation<br />

and backfill required for fire water systems; not work of this section.<br />

2. Refer to Division-3 section 03300 for concrete work required for fire water systems;<br />

not work of this section.<br />

3. Refer to Division-15 section 15500 "Fire Protection" for interior building systems<br />

including sprinklers and standpipes; not work of this section.<br />

1.2 QUALITY ASSURANCE:<br />

A. Codes and Standards:<br />

1. NFPA Compliance: Install fire water systems in accordance with NFPA 24 "Standard<br />

for Installation of Private Fire Service Mains and Their Appurtenances".<br />

B. Local Fire Department/Marshall Regulations: Comply with governing regulations pertaining to<br />

hydrants, including hose unit threading and similar matching of connections.<br />

C. UL Compliance: Provide fire hydrants that comply with UL 246 "Hydrants for Fire-Protection<br />

Service", and are listed by UL.<br />

1.3 SUBMITTALS:<br />

A. Product Data: Submit manufacturer's technical product data and installation instructions for<br />

fire water system materials and products.<br />

B. Maintenance Data: Submit maintenance data and parts lists for fire water system materials<br />

and products. Include this data, product data, shop drawings, and record drawings in<br />

maintenance manual; in accordance with requirements of Division 1.<br />

PART 2 - PRODUCTS<br />

2.1 IDENTIFICATION:<br />

A. Underground-Type Detectable Warning Tape: Manufacturer's standard permanent,<br />

bright-colored, continuous-printed plastic tape, intended for direct-burial service; not less than<br />

6" wide x 4 mils thick. Provide blue tape with black printing reading "CAUTION WATER LINE<br />

BURIED BELOW".<br />

2.2 PIPES AND PIPE FITTINGS:<br />

A. Provide materials and products complying with NFPA 24 where applicable. Provide sizes<br />

and types matching piping and equipment connections; provide fittings of materials which<br />

match pipe materials used in fire water piping systems. Where more than one type of<br />

materials or products is indicated, selection is Installer's option.<br />

B. Piping: Provide pipe fittings and accessories of same material and weight/class as pipes,<br />

with joining method as indicated. Minimum size of Fire Main serving Building Fire sprinkler<br />

system on Fire Hydrants shall be 6 inches in diameter.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION MARCH 2, 2009<br />

FIRE WATER SYSTEM 02668 - 1