K. Undercabinet and similar fixtures are to be hard wired. Flexible cords similar to SO cord are<br />

not acceptable.<br />

L. Air supply fixtures shall be supplied with pattern control vanes.<br />

M. See Architectural plans for fire rated ceilings and coordinate fixture installation with general<br />

contractor to assure continuity of fire rating.<br />

N. Do not mount fluorescent or H.I.D. fixtures within 12" of any cable tray or telecommunications<br />

cable.<br />

O. Where dimming systems are specified, contractor shall operate fixtures at full intensity for a<br />

minimum of 100 hours prior to testing. Lamps shall not be dimmed until the 100 hours is<br />

complete.<br />

END OF SECTION<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

LIGHTING Section 16500-6