size and weight moves only within or a maximum distance of twelve inches either in a<br />

horizontal or vertical manner at the approximate speed of 12 inches per second. The sum of<br />

this distance, volume and speed represent the average condition an Occupancy Sensor must<br />

meet in order that the lights will not go off when a person is reading or writing while seated at<br />

a desk.<br />

D. Sensors will cover a minimum of 1500 square feet when mounted at 12 feet.<br />

E. The sensors are designed to be ceiling mounted and not protrude more than 2 inches and<br />

should blend in aesthetically with the space.<br />

F. Each sensing technology shall have independent sensitivity adjustments and LED display.<br />

G. Time Delay range shall be adjustable from 15 seconds to 15 minutes.<br />

H. Sensors shall operate on 24 volts, 25 milliamps DC.<br />

I. Sensor shall have an additional single pole, double throw isolated relay with Normally Open,<br />

Normally Closed and Common outputs rated at 1 amp for 24 VDC. The isolated relay is for<br />

use with HVAC control, Data Logging, and other control options.<br />

J. Ultrasonic circuit shall be solid state, crystal controlled with signal processing filtering.<br />

K. Ultrasonic receivers shall be temperature and humidity resistant with less than a 6dB shift in<br />

the humidity range of 10% to 90% and less than a 6dB shift in the temperature range of -20o<br />

to 60o C.<br />

L. The ultrasonic frequency shall be 40 kHz + .006%.<br />

M. Ceiling mount sensors shall provide a minor motion coverage range of 250 to 1300 square<br />

feet with an overall 1/2 step coverage range from 500 to 2000 square feet.<br />

N. All sensors shall be capable of operating normally with electronic ballast and PL lamp<br />

systems.<br />

O. All sensors shall be self-contained, crystal controlled ultrasonic or infrared occupancy<br />

sensors located to provide coverage of 90 to 100% of the controlled area.<br />

P. Coverage of sensors shall remain constant after sensitivity control has been set. No<br />

automatic reduction shall occur in coverage due to the cycling of air conditioner or heating<br />

fans.<br />

Q. All sensors shall have readily accessible, user adjustable controls for time delay and<br />

sensitivity. Controls shall be recessed in the sensor to limit tampering.<br />

R. In the event of failure, a bypass manual "override on" shall be provided on each sensor.<br />

When bypass is utilized, lighting shall remain on constantly or control shall divert to a wall<br />

switch until sensor is replaced. This control shall be recessed in the sensor to prevent<br />

tampering.<br />

S. Ultrasonic operating frequency shall be crystal controlled to within plus or minus 0.005%<br />

tolerance to assure reliable performance.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

OCCUPANCY SENSED LIGHTING CONTROL 16550-4