A. Remote identification module devices shall be attached to any single normally open initiating<br />

device (heat detector, waterflow switch, duct detectors, sprinkler, tamper switches, kitchen<br />

hood, pull station, etc.). The modules shall supply addressing and status information to the<br />

Fire Alarm Control Panel through the dual loop module.<br />

2.7 CONTROL POINT MODULE: AOM-2RF:<br />

A. The control point module shall be connected to the same loop as the initiating devices, and<br />

shall provide (2) seperate relay output (Form "C" 2 Amp @ 24 VDC, resistive only).<br />

B. This relay output shall be used to perform auxiliary functions.<br />

C. When the AOM is activated, the red "ACTIVE" LED shall be on solid. Under normal<br />

conditions, the green "ON LINE" LED shall flash.<br />

2.8 MANUAL FIRE ALARM STATION: MS-7AF:<br />

A. Provide red enclosure, manual fire alarm stations with the following features:<br />

1. Addressable alarm type electrically compatible with system<br />

requirements.<br />

2. Double Action<br />

2.9 SMOKE DETECTORS: ASD-IL2F:<br />

3. 1 viewable LED to indicate the status of the device<br />

4. Break glass design requiring unit to be opened for resetting, and<br />

requiring resetting before closing. Provide one spare “glass” for each<br />

manual station. Key reset, keyed like fire control panel.<br />

A. All ionization smoke detectors shall be capable of being replaced without disconnecting any<br />

wires or wire connectors from the base of the detector. Each detector shall be installed on a<br />

separate base. The detector base shall be capable of receiving a photoelectric, ionization, or<br />

electronic thermal detector. All ionization fire detectors shall be UL 268 listed. All detectors<br />

shall have (2) viewable LEDs to indicate the status of the device.<br />

2.10 DUCT FIRE DETECTORS: ADP-RF:<br />

A. Provide photo electronic type with UL 268A listings. Each detector shall be equipped with a<br />

remote light. Each detector shall have (2) form "c" alarm contacts rated at 10 amps (at<br />

120VAC).<br />

2.11 BEAM SMOKE DETECTORS: ABD-2F:<br />

A. Provide addressable projected beam smoke sensor, with each detector consisting of a<br />

transmitter and receiver combination unit with reflector. The transmitter/receiver head shall<br />

be capable of being located up to 328 feet from the reflector. Provide on wall mounted arms<br />

as shown.<br />

2.12 THERMAL DETECTORS: ATD-RL2F:<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

FIRE ALARM SYSTEMS 16723-7