Ducts, unless otherwise approved, shall conform accurately to the dimensions indicated on the drawings,<br />

and shall be straight and smooth on the inside with joints neatly finished. All duct sizes shown on the<br />

drawings are free area inside dimensions. Acoustically-lined ducts shall have outside dimensions increased<br />

as<br />

required to accommodate the acoustic lining specified and still maintain the free area inside dimensions<br />

shown on the drawings.<br />

Under no circumstances shall the cross section of any duct be decreased by dents, pipes, or hanger rods<br />

running through it unless otherwise indicated on the drawings. Neither shall the shape be changed without<br />

approval. No abrupt transitions that restrict the area shall be used. Where necessary to gain clearance, the<br />

duct seams may be turned inside. Structural and Architectural drawings shall be consulted for areas with<br />

restrictive clearances.<br />

FIELD VERIFICATION:<br />

No ductwork shall be fabricated without first field verifying that the available space (under actual job<br />

conditions) will permit installation of the ductwork without structural or other conflicts.<br />

FLEXIBLE CONNECTION:<br />

This contractor shall provide flexible connections not less than 4 inches wide, constructed of heavy,<br />

waterproof, woven plastic-coated glass fabric at the inlet and outlet connections of each fan unit, securely<br />

fastened to the unit and to the ductwork by a galvanized iron band, and provided with tightening screws.<br />

Corners shall be sewn tight shut.<br />

+4" PRESSURE CLASS FLEXIBLE CONNECTIONS:<br />

This flexible connection between the +4" P.C. ductwork and VAV boxes or fans shall be fabricated of<br />

neoprene-coated 1/8 inch glass fabric sheets with the ends vulcanized together. The flexible connection<br />

shall be securely attached to the fan and ductwork with heavy iron draw bands. Connections shall be 30ounce<br />

Ventglass.<br />

AIR FLOW MEASURING DEVICES:<br />

The sheet metal contractor shall install the air flow measuring devices as specified in Section 15900. The<br />

devices will be furnished by the control contractor.<br />

BELT GUARDS:<br />

Belt guards shall be fabricated and installed. Guards shall be constructed of 10-gauge wire, 1-inch mesh in<br />

1-1/2 inch angle-iron welded frames. All guards shall be provided with an opening for a tachometer and<br />

shall be either the split type or easily removable for belt repair. The guards shall be anchored securely to<br />

the floor or walls to prevent any vibration.<br />

-<br />

___________________________________________________________________________________<br />

____________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

AIR DISTRIBUTION 15800 - 5