Materials and construction shall be as specified for water valves sizes 1-1/2-inch and smaller.<br />

On sizes 3/4-inch and smaller ends may be sweat or compression type.<br />

Each station shall be complete with quick disconnect valves and safety shut-off valves, metal identification tag<br />

on chain giving pipe size, meter series, station identification, and meter reading at specified flow rate. Metering<br />

stations shall be selected so that design flow rate shall be between 10 and 40 inches of water pressure<br />

differential with permanent pressure loss of not more than 25% of indicated flow rate differential pressure.<br />

The calibrated flow metering valves shall be selected to deliver the rated flows at the mid-point of their set-point<br />

range.<br />

Venturi Flow Metering System shall be by Barco Engineering Company or Robertson. Calibrated orifice system<br />

shall be Bell & Gossett, Armstrong, Flow-Set, or Taco.<br />

GAS PRESSURE REGULATORS:<br />

Furnish and install, as required, approved type gas pressure regulators in gas piping ahead of appliance and<br />

equipment. Regulators located outside of building shall have weatherproof vent with bugproof screen.<br />

Regulators located inside of building shall be vented thru the roof with approved thread on bug screen.<br />

Approved manufacturers of gas regulators are Fisher and Reliance.<br />

V-BELT DRIVES:<br />

Capacity of V-belt drives at rated RPM shall be not less than 150 percent of motor nameplate horsepower rating.<br />

V-belt drive combinations shall be limited to A, B, C, and fractional horsepower belts. 3V, 5V, and 8V belts and<br />

sheaves shall not be used.<br />

Drives requiring single belt application shall be of the adjustable pitch type. Multiple belt drives shall be of the<br />

non-adjustable type. All fixed pitch sheaves, including single groove fan sheaves, shall be of the bused type.<br />

Fixed bore sheaves will not be acceptable for non-adjustable pitch sheaves.<br />

All belt drives shall be fitted with belt guards.<br />

MAGNETIC STARTERS:<br />

Contractor furnishing pre-wired "packaged equipment" with 1/2 HP and larger motors shall furnish<br />

factory-mounted magnetic starters. Magnetic starters shall provide both overload and undervoltage protection<br />

and shall have integral hand-off-auto switch, auxiliary contacts, and pilot. All motors installed under this contract<br />

shall have a disconnect switch in the immediate vicinity of the motor. Starters on three phase motors shall<br />

protect all three legs of the circuit. Starters to be Cutler-Hammer, Square "D", or Westinghouse.<br />

Starters for all motors on other than "packaged equipment" will be furnished and installed by the electrical<br />

contractor.<br />

______________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDTION March 2, 2009<br />

BASIC MATERIALS & METHODS 15050-15