2.1 ACCEPTABLE MANUFACTURERS:<br />

A. FCI as distributed by Nelson Fire or approved equal.<br />

B. Requests for substitution of other products will be considered if submitted in accordance with<br />

the general conditions and Section 16050.<br />

C. Arrange for the fire alarm system vendor to review the wiring and power supply capacity of<br />

the existing system. Increase the power supply capacity, signal circuit wire size, or add a<br />

remote power supply as needed to accomplish proper operation of the system.<br />

2.2 FIRE ALARM DETECTION SYSTEM<br />

A. GENERAL: Provide an electrically operated, electrically supervised fire alarm system as<br />

described herein. Include control units, power supplies, alarm initiating and indicating<br />

devices, conduit, wire, fittings and accessories required to provide a complete operating<br />

system. Enclose entire system in raceway. Provide basic wiring materials which comply with<br />

Division 16, Basic Materials and Methods Sections for raceways, conductors, boxes, fittings,<br />

supports, etc. Minimum wire size to be #14 AWG copper.<br />

B. SYSTEM TYPE: Analog addressable, non-coded. Either manual activation of a fire alarm<br />

station or activation of an automatic initiating device energizes all fire alarm signaling devices,<br />

sounding a non-coded alarm and providing device identification on an annunciator panel.<br />

C. SYSTEM OPERATION: Provide system such that any manual station or automatic initiating<br />

device annunciates all alarm indicating units (bells, horns, buzzers, chimes, visual alarm<br />

lamps, etc.) continuously until the manual station or initiating device is restored to normal and<br />

the fire alarm control unit reset. Annunciate alarm signals by device at the control panel and<br />

all remote annunciators. Provide all conductors, raceway, equipment and labor to<br />

accomplish the following:<br />

D. Deactivate air supply and return fan units simultaneously by means of a supervised master<br />

fan shutdown relay with slave relays as required. Restart air units automatically after panel<br />

has been reset. Provide a bypass switch for master fan shut down relay for drill purposes,<br />

and indicate by a locked-in lamp that the circuit has been bypassed.<br />

E. Selectively activate and/or deactivate fan units as required.<br />

F. Release all magnetic door holders upon activation of an alarm from any device by use of a<br />

master relay in the control panel.<br />

G. Provide supervised circuits for the following:<br />

1. Close dampers upon activation of an alarm from any device through the HVAC<br />

interface relays at the Fire Command Center.<br />

2. Recall elevators, upon activation of an alarm, to the floor of building egress unless<br />

the alarm is on the egress floor, in which case recall elevator to the level designated<br />

by the Fire Marshal. Cooperate with the elevator supplier to ensure complete<br />

operable system. Provide shunt trip breaker(s) as required.<br />

H. Central Station Monitoring. Provide a UL listed fire control communicator in accordance with<br />

NFPA 71 with a minimum of two reporting zones to the central station. Provide a<br />

communicator with dual phone lines for central station reporting by using BFSK or pulsed<br />

single round fast format. Provide integral trouble annunciator. Provide with compatibility for<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

FIRE ALARM SYSTEMS 16723-3