1. Certification by joint sealant manufacturer that sealants plus the primers and cleaners<br />

required for sealant installation comply with local regulations controlling use of volatile<br />

organic compounds.<br />

C. Samples for initial selection purposes in form of manufacturer’s standard bead samples,<br />

consisting of strips of actual products showing full range of colors available, for each product<br />

exposed to view.<br />

D. Samples for verification purposes of each type and color of joint sealant required. Install joint<br />

sealant samples in ! inch wide joints formed between two 6-inch long strips of material<br />

matching the appearance of exposed surfaces adjacent to joint sealants.<br />

E. Certificates from manufacturers of joint sealants attesting that their products comply with<br />

specification requirements and are suitable for the use indicated.<br />

F. Product test reports for each type of joint sealants indicated, evidencing compliance with<br />

requirements specified.<br />

1.05 QUALITY ASSURANCE<br />

A. Installer Qualifications: Engage an experienced Installer who has completed joint sealant<br />

applications similar in material, design, and extent to that indicated for Project that have<br />

resulted in construction with a record of successful in-service performance, total of 3 years or<br />

more.<br />

B. Single Source Responsibility for Joint Sealant Materials: Obtain joint sealant materials from a<br />

single manufacturer for each different product required.<br />

C. Preconstruction Compatibility and Adhesion Testing: Submit to joint sealant manufacturers,<br />

samples of materials that will contact or affect joint sealants for compatibility and adhesion<br />

testing as indicated below:<br />

1. Use test methods standard with manufacturer to determine if priming and other specific<br />

joint preparation techniques are required to obtain rapid, optimum adhesion of joint<br />

sealants to joint substrates.<br />

a. Perform tests under normal environmental conditions that will exist during<br />

actual installation..<br />

2. Testing will not be required when joint sealant manufacturer is able to submit joint<br />

preparation data required above that are acceptable to Architect and are based on<br />

previous testing of current sealant products for adhesion to, and compatibility with, joint<br />

substrates and other materials matching those submitted.<br />

D. Preconstruction Field Testing: Prior to installation of joint sealants, field-test their adhesion to<br />

joint substrates as follows:<br />

1. Locate test joints where indicated or, if not indicated, as directed by Architect.<br />

2. Testing will not be required when joint sealant manufacturer is able to submit joint<br />

preparation data required above that are acceptable to Architect and are based on<br />

previous testing of current sealant products for adhesion to, and compatibility with, joint<br />

substrates and other materials matching those submitted.<br />

3. Notify Architect one week in advance of the dates and times when mock-ups will be<br />

erected.<br />

E. Pre-Installation Conference: Conduct conference at Project site to comply with requirements of<br />

the Division 1 Section covering this activity.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION MARCH 2, 2009<br />

JOINT SEALANTS 07900-2