10.04.2013 Views

Complete Compiled Specification.pdf - Peck Ormsby Construction

Complete Compiled Specification.pdf - Peck Ormsby Construction

Complete Compiled Specification.pdf - Peck Ormsby Construction

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

I. All materials and equipment installed under this work shall be properly and adequately<br />

supported from the building structure except where ceiling construction or other provisions<br />

are specifically designed to support them. Support systems shall provide a safety factor of<br />

four. This shall apply to chains, hangers, anchors, clamps, screws, structural iron, and all<br />

other hardware and appurtenances associated with the support system.<br />

J. Rough-in for communications outlets for phone and data systems shall consist of a 4" square<br />

deep (4SD) box with a single gang mud ring. A minimum of 1 1/4 inch conduit will be used<br />

for all TELCOM location pathways, and ALL conduits will be routed in the ceiling space and<br />

not in the concrete slab. All conduits will be run from the location in one complete and<br />

continuous path to the cable tray and bonded to the cable tray as per ANSI/TIA/EIA<br />

Standards and the National Electric Code. Refer to data specification for additional details.<br />

K. Maintain the following minimum separations from voice and data cables. Power conduit -<br />

12", transformers and motors - 40", fluorescent lighting - 12". Coordinate with the voice and<br />

data installer to assure these separations are met.<br />

L. All new floor mounted electrical equipment including, but not limited to: Transformers,<br />

Switchboards, MCC’s, Switchgear, Switches, UPS, PDU’s and Generators; shall have<br />

concrete housekeeping pads installed. All Concrete pads shall be as indicated on the<br />

drawings or 4 inches high above finished floor, extending to 4 inches beyond the width and<br />

depth of the Equipment base; pad dimensions indicated on the drawings shall take<br />

precedence in all cases.<br />

3.3 LOW VOLTAGE WIRING METHODS:<br />

A. Provide conduit homeruns complete for all low voltage systems in the new addition and office<br />

remodel area. Plenum cabling will not be acceptable.<br />

B. Provide plenum rated cabling for fire alarm, access control, security, and PA system wiring in<br />

existing school areas with hard ceiling (classrooms, hallways, restrooms, storages, etc.).<br />

Refer to the drawings for details. Wiring to be concealed above ceiling and supported on the<br />

j-hooks.<br />

C. Provide a box, plaster ring, and conduit with insulated bushing from each wall or floor outlet<br />

to an accessible ceiling or crawl space. Conduit shall be minimum 1-1/4" for voice and/or<br />

data outlets, and sized as needed for other systems. Drawings notes shall take precedence.<br />

Raceways for phone and data cable shall be sized based on the number of cables in<br />

accordance with the division 17000 specification.<br />

D. Furnish and install all necessary sleeves and raceways to permit the installation of signal<br />

cables (specific attention is called to non-contiguous ceiling spaces) to the appropriate<br />

equipment termination point. Provide sleeves through all fire-rated walls and partitions. No<br />

outlets of any type shall be left without a raceway system or accessible ceiling path to their<br />

termination point. Verify that raceway sizes and quantities are appropriate and will have at<br />

least 50% spare capacity after all cables are initially installed. Provide at least one empty<br />

spare conduit to each area, sized to handle future needs.<br />

3.4 LABELING:<br />

A. Clearly and properly label the complete electrical system to indicate the loads served or the<br />

function of each item of equipment provided under this work.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

BASIC ELECTRICAL MATERIALS AND METHODS 16050-6

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!