Adhesives, mastics, and coatings shall be applied at the manufacturer's recommended minimum coverage per<br />

gallon.<br />

Where insulation pipes pass thru sound or fire-rated walls, floors, or ceilings, the insulation sleeves shall be<br />

sound or fire-rated to match rating of surface penetrated.<br />

All insulation which runs outside of the building, or inside of the building in areas where the insulation will be<br />

exposed to physical abuse, shall be jacketed with a minimum thickness of .016 inch aluminum. The insulation<br />

and aluminum shall be secured in place by a continuous friction type joint to provide a positive weatherproof seal<br />

along the entire length of the aluminum jacket. Then, an aluminum preformed strap containing a permanently<br />

plastic weatherproof sealant shall be centered over each circumferential joint, and secured by tightening on a<br />

clip, or by use of separate 1/2 inch wide stainless steel banding. All elbows, tube, turns, sweeps, and bends shall<br />

be insulated with mitered sections of aluminum-jacketed insulation. Joints shall be sealed with a sealing<br />

compound and preformed aluminum bands. Valves shall be covered by prefabricated sections of<br />

aluminum-jacketed insulation according to manufacturer's recommendation.<br />

Insulation of storage tanks, manholes, hand holes, and at flanged ends of heat exchangers shall be applied so<br />

that these items can be removed without damaging the insulation.<br />

INSULATION WORKMANSHIP:<br />

All insulation shall be applied by specialists experienced in the field, and shall be neat in appearance. Neatness<br />

in appearance shall be equated to proper insulation application procedures, and sloppy workmanship will not be<br />

tolerated. Work which is deemed unacceptable shall be condemned, removed, and replaced at the contractor's<br />

expense.<br />

Protect floors, valve handle, accessories, etc., to keep paste off areas not being insulated.<br />

Splitting of longitudinal sections on flexible foam pipe insulation will not be permitted.<br />

Do not install insulation on pipes which require heat taping without coordinating with mechanical contractor.<br />

CLEAN-UP:<br />

The piping shall be cleaned and tested prior to installation of insulation.<br />

Fittings shall be cleaned after insulation is installed.<br />

__________________________________________________________________________________________________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

INSULATION 15180-5