VAV supply air damper closed.<br />

b. When the central air handling unit is off, the BAS shall command the<br />

reheat coil hot water valve closed.<br />

c. If the room temperature falls below 50 Deg F. (adjustable), the BAS shall<br />

generate an alarm.<br />

d. Unoccupied Limits<br />

1) Night Low Limit: When the BAS schedule is in the unoccupied<br />

mode the room temperature setpoint shall be reset as follows:<br />

OAT Setpoint<br />

0 Deg F 60 Deg F<br />

32 Deg F 55 Deg F<br />

e. In rooms with convectors, the convector hot water valve shall be<br />

modulated to maintain the night low limit temperature. If a room<br />

temperature falls below the night low limit, the air handler shall be<br />

commanded on and shall continue on and run until the room<br />

temperature rises by 5 degree F (adjustable).<br />

2. Occupied Mode<br />

a. The BAS and the room occupancy sensor shall schedule the VAV to<br />

occupied mode. The central air handling unit must be running before the<br />

VAV will operate in the occupied mode.<br />

b. If the central air handling unit is running before the VAV is scheduled<br />

occupied, the VAV shall be in the warmup/cooldown mode.<br />

c. The cooling setpoint shall be 3 Deg F (adjustable) greater than the<br />

heating setpoint, and the heating setpoint is reset by the following<br />

schedule:<br />

OAT Setpoint<br />

40 F 72 F<br />

68 F 70 F<br />

d. Cooling:<br />

1) The BAS shall modulate the VAV supply air damper to maintain<br />

room temperature of 73 Deg F. Reset with the table above.<br />

2) The supply damper shall be modulated towards the maximum<br />

position as the room temperature rises above setpoint and shall<br />

be modulated towards the minimum position as the room<br />

temperature drops below the setpoint.<br />

3) The VAV shall operate independent of the supply air pressure.<br />

e. Ventilation:<br />

1) In the occupied mode the VAV box shall open to the Ventilation<br />

minimum setpoint.<br />

f. Heating:<br />

1) When the room temperature drops below the heating setpoint,<br />

the VAV Box shall be considered to be in the heating mode.<br />

2) The BAS shall modulate VAV supply air damper to maintain the<br />

heating minimum flow (CFM).<br />

3) When the room temperature drops below the heating setpoint,<br />

the BAS shall modulate the hot water reheat valve to maintain<br />

the heating setpoint of 70 Deg F. (adjustable). The BAS shall<br />

start to open the hot water reheat valve when the room<br />

temperature drops below 70 Deg F. The BAS shall modulate the<br />

hot water reheat valve to the full open position when the room<br />

temperature drops below the heating setpoint by 1 Deg<br />

F. (adjustable). The VAV box shall modulate open to the heating<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION<br />

AUTOMATIC TEMPERATURE CONTROLS 15900-11