MINIMUM PIPE INSULATION<br />

INSULATION THICKNESS IN INCHES FOR PIPE SIZES**<br />

PIPING SYSTEM<br />

TYPES<br />

FLUID<br />

TEMP.<br />

RANGE, F<br />

RUN-<br />

OUTS<br />

2"*<br />

1" &<br />

LESS<br />

1-1/4"<br />

TO 2"<br />

2-1/2"<br />

TO 4"<br />

5" TO 6" 8" +<br />

HOT SURFACE SYSTEMS<br />

Low Press/Temp. 201-250 1 1-1/2 1-1/2 2 2 2<br />

Low Temp. 120-200 1/2 1 1 1-1/2 1-1/2 1-1/2<br />

COOLING SYSTEMS<br />

Chilled Water 40-45 1 1 1-1/2 1-1/2 1-1/2 1-1/2<br />

Domestic Cold Water 40-55 1 1 1 1 1 1<br />

Refrig. or brine Below 40 1 1 1-1/2 1-1/2 1-1/2 1-1/2<br />

* Runouts not exceeding 12 feet in length to individual terminal units.<br />

** For piping exposed to outdoor air, increase thickness by 1/2".<br />

Pipe insulation shall be covered with an all-service jacket.<br />

WATER & WASTE PIPING EXPOSED BELOW ALL LAVATORIES AND SINKS:<br />

Insulate all exposed surfaces with an approved ADA insulation kit as required by sink manufacturer.<br />

ROOF DRAIN PIPING:<br />

Roof drain receivers and roof drain piping (both primary and secondary) except in masonry wall and<br />

where buried in the ground, shall be insulated as specified for domestic cold water. Insulation thickness<br />

shall be 1". Provide white PVC insulation cover for all roof drain piping that runs exposed in occupied<br />

areas.<br />

REFRIGERANT SUCTION PIPING:<br />

Refrigerant suction piping shall be insulated with 1/2" thick closed cell flexible foam. Finish exterior<br />

insulation with two heavy coats of UV resistant gray sealer.<br />

CHILLED WATER PUMPS:<br />

Insulate with removable and replaceable covers consisting of No. 20 gauge galvanized sheet metal jacket lined<br />

with 2" thick high density polystyrene insulation. The insulation shall have an average "K" factor or .22. All voids<br />

between insulation and pump housing shall be filled insulation. Closure joints of metal casing shall be<br />

vapor-sealed after the covers are in place.<br />