B. The TVSS shall be compatible with the electrical system voltage, current, configuration and<br />

intended application.<br />

C. The TVSS maximum continuous operation voltage (MCOV) shall be capable of sustaining<br />

100% of the nominal RMS voltage continuously without degradation.<br />

D. The TVSS shall only use solid state clamping components connected in parallel with the<br />

supply to limit the surge voltages. Clamping components shall be installed in 7 modes. Four<br />

mode TVSS devices are not acceptable.<br />

E. Provide visual or audible indication of properly performing protection.<br />

F. Provide a surge counter.<br />

G. House in the appropriate NEMA rated enclosure or within the switchboard or panelboard as a<br />

complete US listed assembly. Refer to drawings for installation requirements.<br />

H. Warranty shall be for full replacement without pro-rating value, for a minimum period of 5<br />

years.<br />

PART 3 - EXECUTION<br />

3.1 INSTALLATION:<br />

A. Ship with complete installation instructions which are to be followed in detail. The<br />

manufacturer's representative is to be contacted and is to supervise the installation.<br />

B. Installation shall comply with all applicable State and National Electrical Codes, including<br />

NEC Articles 240, 250, 310 and 280. Provide overcurrent protection and a means to<br />

disconnect power from unit. All fuses utilized for the TVSS overcurrent protection shall be of<br />

the Time Delay type rated for the available fault current at the location of installation.<br />

C. Phase, neutral and ground leads of installed TVSS must be grouped and twisted together up<br />

to the point of connection at the bus or overcurrent device. Lead lengths must be as short as<br />

possible, avoiding bends where possible. In no case will lead lengths greater than sixteen<br />

inches or sharp bends in leads be permitted. Lead length is measured from switchboard bus<br />

or breaker to point of connection to TVSS device.<br />

D. Conductors must terminate with compression type lugs.<br />

E. Mount so that suppressor indicator lights will be clearly visible after installation.<br />

F. Overcurrent and disconnect devices shall be exclusively utilized for the TVSS device.<br />

G. Raceway from TVSS to switchboard shall consist of rigid steel conduit with double locknuts<br />

and grounding bushings connected to switchboard ground.<br />

H. Overcurrent protection sizing shall be as per manufacturer’s instructions. Conductor sizing<br />

shall be based on NEC requirements.<br />

END OF SECTION<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

TRANSIENT VOLTAGE SURGE SUPPRESSORS 16478-3