1. Type S-12, bugle head, self-tapping, rust-resistant, fine thread for heavy-steel gauge<br />

(12 to 22).<br />

2. Type S, bugle head, rust-resistant sharp point, fine thread for light-gauge metal<br />

framing or furring.<br />

D. Sealants, caulk and tape:<br />

1. Dow Corning 795, Pecora 895, or equivalent.<br />

2. 2" wide 10 x 10 glass mesh Quick Tape or equivalent<br />

2.06 FABRICATION<br />

A. General: Framing components may be prefabricated into assemblies prior to erection.<br />

Fabricate panels plumb, square, true to line and braced against racking with joints welded.<br />

Perform lifting of prefabricated panels in a manner to prevent damage or distortion.<br />

B. Fabricate panels in jig templates to hold members in proper alignment and position and to<br />

assure consistent component placement.<br />

C. Fastenings: Attach similar components by welding. Attach dissimilar components by welding,<br />

bolting, or screw fasteners, as standard with manufacturer.<br />

D. Wire tying of framing components is not permitted.<br />

E. Fabrication Tolerances: Fabricate panels to a maximum allowable tolerance variation from<br />

plumb, level, and true to line of 1/8" in 10'-0".<br />

PART 3 - EXECUTION<br />

3.01 INSTALLATION<br />

A. General: Install metal framing systems in accordance with manufacturer's printed or written<br />

instructions and recommendations.<br />

B. Runner Tracks: Install continuous tracks sized to match studs. Align tracks accurately to<br />

layout at base and tops of studs.<br />

1. At concrete, attach with Hilti X-DNI47P8 fasteners (or equal) at 12 inches on center,<br />

staggered.<br />

2. At steel beams, attach with Hilti X-DNI27P8 fasteners (or equal) at 12 inches on<br />

center, staggered.<br />

3. Provide fasteners at corners and ends of tracks.<br />

4. Provide slip tracks where top of wall occurs under structural beams. Installation to<br />

accommodate an deflection of ! inch or less.<br />

C. Installation of Wall Studs: Secure studs to top and bottom runner tracks by either welding or<br />

screw fastening at both inside and outside flanges.<br />

1. Screws: #10 minimum.<br />

D. Set studs plumb, except as needed for diagonal bracing or required for non-plumb walls or<br />

warped surfaces and similar requirements.<br />

E. Where stud system abuts structural columns or walls, including masonry walls, anchor ends<br />

of stiffeners to supporting structure.<br />

F. Install supplementary framing, blocking and bracing in metal framing system wherever walls<br />