***All K Type terminations are to use CT-F-C6-02 jacks in specified locations.<br />

2.8 MISCELLANEOUS AREA OUTLETS (FIRE ALARMS, EMERGENCY DIALERS, ELEVATORS,<br />

ENVIRONMENTAL CONTROLS, WIRELESS ACCESS POINTS)<br />

A. 1- 4 PAIR CAT 6 LINE FOR THE ELEVATOR/LIFT- REFER TO PLANS FOR EXACT<br />

LOCATION - terminated one pair per port sequentially on the patch panel.<br />

B. 1- 4 PAIR CAT 6 LINE FOR THE FIRE ALARM, EMERGENCY DIALER REFER TO<br />

ADMINISTRATION AREA PLANS FOR EXACT LOCATION - terminated one pair per port<br />

sequentially on the patch panel.<br />

C. 1- 4 PAIR CAT 6 LINE RAN TO THE ENVIRONMENTAL CONTROLLER (S) AT THE<br />

SCHOOL. IF THERE IS MORE THAN 1 CONTROLLER, LINES NEED TO BE PULLED TO<br />

EACH OF THE LOCATIONS AS SPECIFIED ON THE PLANS, AND MUST HAVE A SIEMON<br />

MX6-02 CONNECTOR INSTALLED ON THE END OF THIS CALBLE LOCATION INSIDE OF<br />

THE ENVIRONMENTAL CONTROLLER BOX.<br />

D. 1- 4 PAIR CAT 6 LINE RAN installed in the center of each of the classrooms, in the center of<br />

the office areas, faculty lounges, work rooms, multipurpose rooms (Gym, Auditorium, Lunch<br />

areas), computer labs, and two individual locations within the media center. Each of these<br />

locations is to have enough service loops on the access point end to get the cable below the<br />

ceiling tile. These access point locations will be numbered and terminated according to the<br />

other locations within each classroom or location.<br />

These locations shall be indicated as a L1 location on the plans, and must be terminated into<br />

a patch panel in the telecommunication room nearest the room being installed, and must have<br />

a SIEMON MX6-02 connector installed on the classroom end so that a wireless access point<br />

can be plugged in<br />

2.9 TERMINATION OF VOICE CABLING IN TELECOMMUNICATIONS ROOM.<br />

A. SIEMON HD6-XX (cabled voice ports plus 25%) 19 in. rack mountable, 24 or 48 port panels<br />

only.<br />

B. Termination of the 25 or 50 pair accordingly, shall patch down on a 24 or 48 port patch bay<br />

respectively with one pair per port. The last pairs of the 25 or 50 pair cable may be rolled<br />

back and tied out of the way so that a 25 or 50 pair may be terminated into a 24 or 48 port<br />

patch panel.<br />

2.10 TERMINATION OF DATA CABLING IN TELECOMMUNICATIONS ROOMS.<br />

A. SIEMON HD6-XX (cabled data ports plus 25% unused ports available) 19 in. rack mountable,<br />

24 or 48 port panels only.<br />

2.11 RACKS AND MANAGEMENT FOR PATCH PANELS AND SWITCHES.<br />

A. Panduit Rack Part #CMR19X84 with Panduit vertical wire management Part #PRV6, Panduit<br />

wire spool Part #PRSP5 for each vertical wire management, and Panduit patch runner dual<br />

hinged door Part #PRD6 for the front and rear of each rack, 19 in. equipment rack, 7 foot 6 in.<br />

overall height with flange base, mounting rails drilled front and back and tapped to EIA<br />

standards. Plan enough racks to accommodate all switches, panels, and managers to a<br />

maximum 70% rack capacity.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

TELEPHONE AND DATA DISTRIBUTION 17000-8