2. Unit-Mounted Non-Fused Disconnect:<br />

Unit shall be supplied with factory-installed, non-fused electrical disconnect for main power<br />

supply.<br />

3. Minimum Load Control:<br />

Unit shall be equipped with factory installed, microprocessor-controlled, minimum load control<br />

that shall permit unit operation down to a minimum of 15% capacity.<br />

4. Energy Management Control Module:<br />

A factory or field-installed module shall provide the following energy management<br />

capabilities:<br />

4 to 20 mA signals for leaving fluid temperature reset, cooling set point reset or demand limit<br />

control and 2-step demand limit control (from 0% to 100%) activated by a remote contact<br />

closure.<br />

5. Condenser Coil Trim Panels and Security Grilles:<br />

Unit shall be supplied with factory or field-installed coil covers and painted grilles to protect<br />

the condenser coil and internal chiller components from physical damage.<br />

6. Hail Guards:<br />

Field-installed accessory kit shall include set of metal grilles for the protection of the<br />

condensing coils from hail damage.<br />

7. BACnet Translator Control:<br />

Unit shall be supplied with field-installed interface between the chiller and a BACnet Local<br />

Area Network (LAN, i.e., MS/TP EIA-485).<br />

8. Touch Display:<br />

9. Freeze Protection Cooler Heaters:<br />

Cooler heaters provide protection from cooler freeze-up to –20 F.<br />

10. Low-Sound Compressor Enclosures:<br />

Provide sound reduction for the scroll compressors through enclosure and blankets not to<br />

exceed the following: Overall sound power level = 90.0 dBA<br />

Distance<br />

from side of<br />

unit (feet)<br />

Free field<br />

sound<br />

pressure<br />

3 75.6<br />

5 73.4<br />

10 69.6<br />

15 66.9<br />

20 64.9<br />

25 63.3<br />

30 61.9<br />

35 60.7<br />

40 59.6<br />

45 58.7<br />

50 57.9<br />

55 57.1<br />

60 56.4<br />

65 55.7<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

HEATING-COOLING 15700-6