A. Provide supplementary notification appliance circuit panel(s) as required. The ‘SNAC’ shall<br />

be capable of supplying up to four Class A, Style Z notification appliance circuits. The panel<br />

shall contain its own battery charger, regulated power supply, and shall be supervised for<br />

ground fault, overcurrent, open circuits and low battery conditions. Ground fault, battery and<br />

circuit trouble conditions shall transmit a trouble signal to the main fire alarm control panel.<br />

2.19 SYSTEM CONFIGURATION PROGRAMMING:<br />

A. To help the owner in programming, system changes, and servicing, the fire alarm system<br />

shall have the following functions:<br />

2.20 BATTERIES/POWER SUPPLIES:<br />

1. The FACP shall be capable of an auto-configuration of the Signal Line<br />

Circuits, which via a password, all analog devices and panel modules are<br />

automatically programmed into the system. At this point the system will<br />

operate as a general alarm system without any other programming.<br />

2. If any two devices are addressed the same, the LED's on both devices<br />

will light steady and the panel will read "extra address and the address<br />

number".<br />

3. If any device is installed and not programmed into the system the LED<br />

will light steady and the panel will read the same as above.<br />

A. Provide standby batteries capable of operating fire alarm system for minimum of 24 hours,<br />

then operating all indicating units for at least five minutes. Locate batteries in fire alarm<br />

control unit, or in similar type enclosure located as directed. Provide all interconnecting<br />

wiring. Place batteries which vent hydrogen gas in separate enclosure. Provide 30 percent<br />

spare capacity.<br />

PART 3 - EXECUTION<br />

3.1 WIRING:<br />

A. Furnish and install all required wiring in accordance with local and National codes.<br />

B. Unless otherwise specified, minimum wire size shall be 16 gauge for audible alarm circuits,<br />

and 18 gauge for signal initiating circuits. All wiring shall be in conduit. Conduit shall be<br />

sized by the contractor. See 16050 for wiring methods.<br />

C. Provide a minimum of one 3/4" conduit with (8) wires #14’s to security panel.<br />

D. Confirm that the existing power supply and circuiting have sufficient capacity to handle<br />

additional horns and strobes. If insufficient capacity exists, add additional components to<br />

resolve the problem. This might include such items as replacing existing signal circuits with<br />

larger wire or replacing power supplies. All signal devices must operate properly at<br />

completion.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

FIRE ALARM SYSTEMS 16723-9