SECTION 16723 – FIRE ALARM SYSTEMS<br />

PART 1 - GENERAL<br />

1.1 WORK INCLUDED:<br />

A. The Contractor shall furnish and install fire alarm devices, as specified herein and indicated<br />

on the drawings.<br />

B. Replace existing main fire alarm control panel. Extend all existing fire alarm initiating,<br />

notification, auxiliary power, and relay shout down circuits to new head end equipment<br />

location. Add additional horn/strobe power supplies as required to accommodate new and<br />

existing initiating and warning devices (detectors, call stations, strobes, horns, tamper<br />

switches, door holders, etc.).<br />

C. Provide all signal initiating devices, audible and visual alarm devices, power supply, a wiring<br />

system, and all accessory devices required to provide a complete operating system.<br />

D. All components shall be compatible with the existing system.<br />

E. Provide new duct smoke detectors and fan relays at all fan units 2000 CFM and over. Shut<br />

down all supply and return fans upon a general alarm signal.<br />

F. Provide vandal resistant cages to protect horn/strobes, smoke and heat detectors as<br />

indicated and in gyms whether shown or not. Securely fasten security cages as required.<br />

Provide backing and bracing as required to insure that attachment extends beyond the ceiling<br />

materials. Cages shall have two pieces, one backplate and one cover to attach to backplate.<br />

Provide cages/guards on horn/strobes that are clear and do not limit their effect on the field<br />

performance with the listing requirements.<br />

G. The system shall comply with the applicable provisions of the National Alarm Code (NFPA<br />

72), Americans with Disabilities Act, and meet all requirements of the local authorities having<br />

jurisdiction. All equipment and devices shall be listed by the Underwriter's Laboratories, Inc.,<br />

or approved by the Factory Mutual Laboratories.<br />

H. Comply with NEC as applicable to construction and installation of fire alarm and detection<br />

system components and accessories. Provide components and systems, which are UL-listed<br />

and labeled for fire alarm. Provide fire alarm and detection systems and accessories, which<br />

are FM approved. Comply with State and local requirements as applicable.<br />

I. Ensure that the fire alarm supplier has a minimum of (1) NICET level four and (3) NICET level<br />

three technicians on staff.<br />

J. Comply with applicable provisions of current NFPA Standard 72 National Fire Alarm Code (as<br />

applicable), local building codes, and meet requirements of local authorities having<br />

jurisdiction.<br />

1.2 RELATED DOCUMENTS:<br />

A. Drawings and general provisions of Contract, including General and Supplementary<br />

Conditions and Division-1 <strong>Specification</strong> sections, apply to work of this section.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

FIRE ALARM SYSTEMS 16723-1