SECTION 16550 – OCCUPANCY SENSED LIGHTING CONTROL<br />

PART 1 - GENERAL<br />

1.1 WORK INCLUDED:<br />

A. The Contractor shall provide all labor, materials, tools, appliances, control hardware, sensor,<br />

wire, junction boxes and equipment necessary for and incidental to the delivery, installation<br />

and furnishing of a completely operational occupancy sensor lighting control system, as<br />

described herein.<br />

B. The Contractor shall examine all general specification provisions and drawings for related<br />

electrical work required as work under Division 16.<br />

1.2 SUBMITTALS:<br />

A. Submit complete and descriptive shop drawings including floor plans, layouts, catalog cuts<br />

and other descriptive data indicating compliance with the specifications herein. Submit data<br />

sheets on sensors, control units and all junction boxes and mounting accessories, including<br />

all wiring diagrams. Provide a complete layout of occupancy sensors including: location,<br />

coverage pattern, direction, and type. Submit in accordance with Section 01300.<br />

PART 2 - PRODUCTS<br />

2.1 ACCEPTABLE MANUFACTURERS:<br />

A. The Watt Stopper, Inc., Mytech/Hubbell, Leviton, Novitas<br />

B. Requests for substitution of other products will be considered if submitted in accordance with<br />

the general conditions and Division 1.<br />

C. All sensors shall be California Energy Commission Title 24 approved and certified.<br />

2.2 WALL SWITCH INFRARED TYPE (For Offices up to 150 square feet).<br />

A. Wall switch sensors shall be capable of detection of motion at desk top level up to 500<br />

square feet.<br />

B. Wall switch sensors shall accommodate loads indicated on the plans.<br />

C. Coverage of 180 degrees<br />

D. Digital auto-OFF time delay adjustable from 30 seconds up to 30 minutes.<br />

E. Adjustable unit sensitivity.<br />

F. Integrated light level sensor - works from 2.4 to 300 footcandles<br />

G. LED for sensitivity calibration<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

OCCUPANCY SENSED LIGHTING CONTROL 16550-1