K. The outside air dampers and relief air dampers shall close completely whenever the<br />

supply and return fans are off and/or when the system is in the UNOCCUPIED or<br />

WARMUP modes.<br />

L. A low limit freeze protection thermostat shall stop the fan if the mixed air temperature<br />

drops below 38 F. and the heating hot water system pump(s) shall start.<br />

M. Smoke detectors shall be incorporated into the building fire alarm system in accordance<br />

with NFPA 90A. Both supply fans shall stop if the building fire alarm system is activated.<br />

Refer to the Fire Alarm System.<br />

N. Provide fire alarm interface relays of the proper coil voltage in the fan systems ATC<br />

panels to stop the supply fans whenever the building fire alarm system is in alarm.<br />

Control power to these relays will be provided by Division 16.<br />

0. The night PURGE mode for each fan system shall be initiated by manual commands<br />

from the District. When these commands are received, each fan system shall be<br />

switched to the OCCUPIED mode. Discharge temperature setpoints shall set to 52 Deg<br />

F. PURGE mode shall continue until the temperatures at the fan system space<br />

temperature sensors drops to 74 F.<br />

P. Once the fan systems space temperatures have reached PURGE setpoint, the fans shall<br />

stop until the regularly scheduled OCCUPIED mode begins.<br />

Q. The WARM-UP mode for the building shall be initiated by a manual command from the<br />

District. When this command is received, fan system shall be switched to the<br />

OCCUPIED mode but the outdoor and relief air dampers shall remain closed. WARM-UP<br />

mode shall continue until the return air temperature at both fan systems has risen to 68 F.<br />

R. Once the fan system return air temperatures have reached WARM-UP setpoint, fan<br />

systems shall switch to the regular OCCUPIED mode.<br />

S. In Unoccupied Mode, the supply and return fans start when the lowest space temperature<br />

drops below the night setpoint temperature and runs until the lowest space temperature<br />

rises 50 Deg F above the night setpoint temperature.<br />

T. Provide a differential pressure transmitter with its sensing tips located across fan system<br />

filter bank.<br />

U. Provide software to provide an alarm to the District Host if the filter differential pressure<br />

continuously exceeds a software setpoint for 15 minutes.<br />

4.7 BUILDING PRESSURIZATION<br />

A. Positive building differential pressure of 0.05 inches w.c. is maintained by modulating the<br />

relief air damper at the roof hoods. The relief damper shall modulate to maintain building<br />

static pressure.<br />

B. Upon shutdown of the air handling unit system relief air dampers shall close.<br />

4.8 UNIT HEATER CONTROL<br />

A. A room thermostat shall cycle a normally open heating valve to maintain desired space<br />

temperature. A strap-on aquastat on the supply pipe will not allow the fan to operate<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION<br />

AUTOMATIC TEMPERATURE CONTROLS 15900-15