For feeders 601 Amps to 6000 Amps:<br />

Class L, KRP-C, KLPC, & A4BQ<br />

For feeders 600 Amps and less:<br />

Class RKk-1 for 600 volt; LPS-RK, LLS-RK, & A6D-R<br />

Class RK-1 for 250 volt; LPN-RK, LLN-RK, & A2D-R<br />

Class J; JHC, JTD, & AJT<br />

For motor circuits beyond the main and subdistribution boards, 600 volt and below:<br />

Class RK-5 for 600 volt; FRS-R, FLS-R, & TRS-R<br />

Class RK-5 for 250 volt; FRN-R, FLN-R, & TR-R<br />

E. SPARE PARTS: Provide 10% spare fuses, but not less than 3 of any one size and type.<br />

F. Provide Spare Fuse Cabinet(s), #SFC, #LSFC, & ATFC as required. Install cabinet(s) in<br />

Main Electrical Room.<br />

G. Approved Manufacturers, with catalog numbers listed in order: Bussman, Littelfuse, Ferraz<br />

Shawmut.<br />

H. If the electrical contractor wishes to furnish materials other than those specified, a written<br />

request, along with a complete short circuit and selective coordination study, shall be<br />

submitted to the engineer for evaluation at least 8 days prior to the bid date. If the engineers<br />

evaluation indicates acceptance, a written addendum will be issued listing the other<br />

acceptable manufacturer.<br />

2.4 BOXES:<br />

A. Outlet and junction boxes shall be sized in accordance with code requirements or as noted<br />

on the drawings.<br />

B. Unless otherwise specified or shown on the drawings, all outlet boxes for new work shall be<br />

galvanized steel knockout, outlet boxes. Gangable boxes are not acceptable. Outlet boxes<br />

shall not be smaller than 4" square and 1-1/2 inches in depth, unless otherwise noted. All<br />

outlet box covers, rings, or other fittings shall be galvanized. Boxes which are exposed to the<br />

weather shall be cast metal. Outlet boxes for phone and data outlets shall be 2.5" deep<br />

boxes.<br />

C. Outlet boxes shall be designed for the intended use, and shall be installed flush with finish<br />

surface lines or not more than 1/8 inch back and shall be level and plumb. Long screws with<br />

spaces or shims for mounting devices are not acceptable. No combustible materials shall be<br />

exposed to wiring at outlets.<br />

D. Outlet boxes on opposite sides of fire or sound isolating partitions shall have a minimum<br />

horizontal separation of 24". Back to back boxes are not permitted in any walls.<br />

E. Unless indicated otherwise on the drawings, floor boxes shall be Walker RFB4 with RAKMII<br />

flush access hatch with carpet trim. Where located in tile floors, provide FAKMII cover.<br />

Provide cast iron for on grade applications, and stamped steel for above grade applications.<br />

Provide shallow stamped still if suspended slab thickness is less than 5-1/2 inches. Provide<br />

plates for mounting of duplex receptacles and RF-45 communications outlets. If the number<br />

of communications outlets exceeds the quantity which fits in a standard plate, provide a<br />

custom plate to accommodate the increased quantity.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

BASIC ELECTRICAL MATERIALS AND METHODS 16050-4