PRE-MANUFACTURED DUCTS:<br />

Runouts above ceiling from primary supply air ducts to VAV terminal boxes may be rigid conduit or premanufactured<br />

high pressure flex duct or a combination of the two.<br />

Runouts above ceiling from the terminal boxes to the ceiling diffusers shall be similar to "Genflex - Type IL".<br />

Maximum allowance length is 5'-0" in any given duct run. Duct to be factory fabricated with spring steel wire<br />

helix and 1" thick glass fiber insulation covered with external vapor barrier and lined with continuous nonperforated<br />

inner sleeve.<br />

Material shall comply with UMC Standard 10-1.<br />

RECTANGULAR DUCT LINING:<br />

The interior surface of all rectangular supply, return, make-up, outdoor, fresh, relief, and exhaust air ducts<br />

(except where noted otherwise), shall be lined with 1" thick fiberglass dual density duct liner, having an<br />

average "K" factor of .24 BTU at 75 deg. F mean. The liner shall meet standards NFPA No. 90A and No.<br />

90B and shall have the Underwriters' Laboratories, Inc., label.<br />

Duct liner shall be applied to the flat sheet with a 100% coverage of duct adhesive. The duct liner shall be<br />

cut to assure snug corner joints. The black surface of the liner shall face the air stream. On horizontal runs,<br />

tops of ducts over 12" in width and sides over 16" in height shall be additionally secured with welded pins<br />

and speed clips on a maximum of 15" centers. On vertical runs, gripnails or welded pins and speed clips<br />

shall be spaced on a maximum of 15" centers on all width dimensions over 12". Pins shall start within 2" of<br />

all cross joints within the duct section.<br />

Welded pins shall be cut virtually flush with the liner surface. Clips should be drawn down flush only and not<br />

so as to compress the liner and cause the leading edge of raise. All exposed edges and the leading edge of<br />

all cross joints of the liner shall be coated with adhesive.<br />

Material shall comply with UMC Standard 10-1.<br />

BOILER STACKS & BREECHINGS:<br />

Stack shall be double wall insulated positive pressure type as shown on plans, with necessary wall brackets,<br />

tee sections, cleanout doors, section bands, trim and fittings for a complete installation. Stack shall have 1"<br />

insulation, stainless steel liner and aluminized steel shell coated for field painting by the painting contractor.<br />

Stack shall be Metalbestos Model PS (UL listed).<br />

REGISTERS, GRILLES AND DIFFUSERS:<br />

Supply Air Diffusers:<br />

Furnish and install all supply air diffusers shown and specified on the drawings. All units to have opposed<br />

-<br />

___________________________________________________________________________________<br />

____________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

AIR DISTRIBUTION 15800 - 6