Work Included Elsewhere:<br />

Underground Mains: N.F.C. #24<br />

Concrete Work - by General Contractor<br />

Access Doors - By General Contractor.<br />

Color coding or pipe identification - By Mechanical Contractor.<br />

Wiring of flow switches and gate valve supervisory switches - By Electrical Contractor.<br />

WORK BY FIRE PROTECTION CONTRACTOR:<br />

This contractor shall furnish and install all labor, material, and equipment to make a complete and working fire<br />

protection system fully tested and approved in accordance with the drawings, standards of this specification for<br />

the new building, and minor system modifications in the existing building.<br />

UNDERGROUND WATER SUPPLY:<br />

Fire protection contractor shall perform a flow test at or near site prior to final calculations for system. Flow test to<br />

be performed in the presence of the state or local fire marshal and Alpine School District representative.<br />

System Flow Data:<br />

Static Pressure 75 psi<br />

Residual Pressure 70 psi<br />

Flow 1,100 gpm<br />

Sprinkler System:<br />

This system shall conform to N.F.C. #13 and #14 and I.B.C. Riser may be calculated, but shall not be smaller<br />

than 6". Sprinkler systems are to be light, ordinary, or extra hazard, as required by NFC-13 and the Utah State<br />

Fire Marshall's office.<br />

System shall be hydraulically calculated. Sprinkler system shall be light hazard, except for casual ordinary and<br />

extra hazard group 1 in storage and service areas. Density for light hazard areas shall be 0.10 gpm per sq. ft.<br />

over 1500 sq. ft. Remote area with a maximum head spacing of 225 sq.ft. Service area shall be density of 0.15<br />

over 2000 sq. ft. with maximum spacing of 130 sq. ft.<br />

QUALIFICATION OF DESIGNER:<br />

Designer shall be an engineering technician or Senior Engineering Technician (Level III or Level IV), NICET<br />

certification for fire sprinkler system design.<br />

QUALIFICATION OF INSTALLER:<br />

It is intended that the system be designed and installed by a firm regularly engaged in the design and installation<br />

_______________________________________<br />

_______________________________________________________________________________________<br />

______<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

FIRE PROTECTION 15500-2