mechanical contractor shall be left without mark, scratch, or impairment to finish upon completion of job. Any<br />

necessary refinishing to match original shall be done. Do not paint over nameplates, serial numbers, or other<br />

identifying marks.<br />

Mechanical Contractor: Spot painting for application of pipe and equipment identification markers.<br />

Mechanical Contractor: Gas piping on roof and exterior walls shall be painted gray with two coats of U. V.<br />

resistant coating.<br />

Painting Contractor: All insulated piping and all piping in equipment rooms of finished areas shall be painted, as<br />

required by the painting specifications. Colors to be selected by owner.<br />

Coding, Pipe Identification & Painting:<br />

All pipes are to be labeled and color coded with contents clearly identified and arrows indicating direction of flow.<br />

Pipes shall be identified at the following locations:<br />

1. Adjacent to each valve.<br />

2. At every point of entry and exit where piping passes thru wall or floor.<br />

3. Every 50 feet on long continuous lines.<br />

4. On each riser and junction.<br />

5. Adjacent to all special fittings or devices (regulating valves, etc.)<br />

6. Connection to equipment.<br />

7. Every 50 feet on roof mounted piping.<br />

Apply markers to they can be read from floor.<br />

Labels and markers shall be of the self-sticking, all temperature permanent type as manufactured by W. H.<br />

Brady Co., 727 West Glendale Avenue, Milwaukee, Wisconsin, or Seton Name Plate Corp., 592 Boulevard, New<br />

Haven, Connecticut.<br />

Pipe color coding shall be uniform throughout.<br />

Background colors shall be as follows:<br />

Yellow: Dangerous Materials (high pressure steam, natural gas condensate, etc.)<br />

Red: Fire Protection Equipment (fire sprinkler water, fire protection water)<br />

Bright Blue: Protective Materials (filtered water)<br />

Green: Safe Materials (heating water, cold water, instrument air, sanitary sewer, etc.)<br />

Letters of identification legend shall be 2" high for pipes 3" and larger, and 1" high for pipes 2-1/2" and under.<br />

Markers shall be installed in strict accordance with the manufacturer’s instructions.<br />

______________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDTION March 2, 2009<br />

BASIC MATERIALS & METHODS 15050-24