PIPE SPECIALTIES FOR GROOVED END PIPE:<br />

Strainer:<br />

Strainers 2" to 12" shall be Victaulic 730 "Vic-Strainer". Straight through pattern, ASTM A536 ductile cast iron<br />

body with grooved ends, 304 stainless steel 20 mesh screen, 0.033" openings. Provide ball valve on drain<br />

connection and run drain line to nearest floor drain.<br />

Suction Diffuser:<br />

Suction diffusers shall be Victaulic 731, one piece ASTM A-536 ductile cast iron or ASTM A-47 malleable iron<br />

body with outlets drilled, tapped, and plugged either side for pressure or temperature gauges and at the bottom<br />

for drain connection. Access end cap shall be of the same material as the body.<br />

Basket shall be of type 304 stainless steel 0.041" wire in a woven no. 6 mesh wire screen with 0.126" opening,<br />

welded securely to a heavy frame of like material, in a convoluted configuration.<br />

Flange connection to pump shall mate to ANSI Class 125 or Class 150 pump flange.<br />

Dielectric Waterway:<br />

Dielectric waterways shall be Victaulic 47 or Perfection Corporation, ASTM A-120, standard weight, galvanized<br />

steel, Schedule 40 pipe with grooved by threaded ends. PVC lining permanently bonded to the interior of the<br />

pipe.<br />

Flow Metering System:<br />

Flow measuring systems shall be Victaulic 733 Venturis Sensor or 734, 734S Orifice/Indicators. Grooved end<br />

type designed to accept grooved mechanical coupling without field preparation. Meters and sensors are<br />

designed for 250 psig working pressure. Venturis sensors to be compatible with systems having flows of 2 GPM<br />

and larger. To be used in systems that require water balancing. Orifice/Indicators shall be used for systems<br />

requiring flow measuring devices.<br />

Vic-O-Let:<br />

Strapless outlet shall be Victaulic 923 cast of ductile iron conforming to ASTM A-536 or malleable iron<br />

conforming to ASTM A-47. Rated at 300 psi working pressure. Gasket shall be for the specific service as<br />

recommended by the manufacturer. Collar shall be hot rolled, pickled and oiled steel conforming to ASTM<br />

A-569.<br />

Vic-O-Well:<br />

Strapless outlet shall be Victaulic 924 cast of ductile iron conforming to ASTM A-47. Rated at 300 psi working<br />

pressure. 6" insertion well. Gasket shall be for the specific service as recommended by the manufacturer.<br />

Collar shall be hot roller, pickled and oiled steel conforming to ASTM A-569.<br />

AUTOMATIC VALVES AND WELLS:<br />

The mechanical subcontractor shall install the automatic temperature control valves, temperature sensing wells,<br />

and flow switches, as directed by the automatic temperature control subcontractor.<br />

UNIONS:<br />

______________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDTION March 2, 2009<br />

BASIC MATERIALS & METHODS 15050-12