VALVE IDENTIFICATION CHART<br />

NUMBER DESCRIPTION LOCATION NORMAL<br />

POSITION<br />

1. Cold Water Supply to Water Heater Mech. Room #121 Open<br />

2. Cold Water Supply to Hose Room #13 Open<br />

3. Cold Water Supply to Equip. in Room<br />

#12<br />

Room #18 Open<br />

4. Sprinkling System Drain Valve Tunnel Below Room #115 Closed<br />

5. Hot Water Supply to Toilet Room<br />

#212<br />

6. Air Vents - Cooling Coil #12 (2<br />

required)<br />

7. Heating Hot Water Balancing Valve<br />

(Southwest Zone)<br />

Mechanical Equipment & Ductwork:<br />

Chase #210 Open<br />

Fan Room 3122 Closed<br />

Above Ceiling Room #412 Marked On<br />

Valve<br />

All mechanical equipment, including meters, fans, pumps, relocated equipment, and other devices shall be<br />

identified with signs made of laminated plastic 1/8" or larger engraved letters. Signs shall be securely attached<br />

by rustproof screws or some other permanent means (no adhesives).<br />

Information on sign shall include name of equipment, rating, maintenance instructions, and any other important<br />

data not included on factory attached nameplate.<br />

Signs shall be attached to equipment so they can be easily read.<br />

Identify all ducts exposed in mechanical equipment rooms and in ducts and pipe chases. Sample duct<br />

identification shall be as follows:<br />

"Cold Duct - High Pressure - To Second Floor System"<br />

"Exhaust Duct - Toilet Room - To EF-3"<br />

"Ventilation Air Duct - To Utility Room #228"<br />

Ducts shall be labeled at all wall penetrations and at connections to equipment.<br />

PAINTING:<br />

Mechanical Contractor: All equipment which is to be furnished in factory prefinished conditions by the<br />

______________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDTION March 2, 2009<br />

BASIC MATERIALS & METHODS 15050-23