B. Requests for substitution of other products will be considered if submitted in accordance with<br />

Section 01630.<br />

2.2 CABLES:<br />

A. Each reel of coaxial cable used in the system shall be sweep tested for transmission and<br />

structural return loss and be so certified in writing by the cable manufacturer. Transmission<br />

sweep tests shall establish conformance to guaranteed loss values from 20-108 MHz, 174-<br />

216 MHz and 470-890 MHz. Structural return loss tests by sweep method shall show a<br />

minimum, return loss of 26 dB RL VHF, 16 dB RL UHF as compared to a fixed 75-ohm<br />

reference from 20-108 MHz, 174-216 MHz and from 470-890 Mhz.<br />

B. Coaxial cables shall be run in continuous lengths except for terminations and no splices shall<br />

be permitted in any conduit run. Cables shall be installed to avoid sharp bends or physical<br />

distortion.<br />

C. Individual drops to rooms shall be West Penn 25841 (RG-6U). Main trunk runs shall be West<br />

Penn 25821 (RG-11) or as specified on the drawings, with drawing notes taking precedence.<br />

D. Cable shall be approved for air plenum use if required by the construction.<br />

2.3 SPLITTERS:<br />

A. Two-way line splitters shall have a flat frequency response over the entire operating band<br />

from 12 MHz to 300 MHz and from 470 to 890 MHz. The unit shall be of the hybrid design<br />

with a 75 ohm match of 23.0 dB RL minimum on all inputs and outputs. Output isolation shall<br />

be not less than 23.0 dB VHF - 18.0 dB UHF.<br />

B. Two-way line splitters shall have a signal loss of not more than VHF 3.7 dB UHF 4.0 dB at<br />

each output. All unused outputs on the splitters shall be terminated with 75 ohm termination.<br />

C. Four-way line splitters shall have a flat frequency response over the entire operating band<br />

from 12 MHz to 216 MHz and from 470 to 890 MHz. The unit shall be of the hybrid design<br />

with a 75 ohm match of 24.0 dB RL minimum on all input and outputs. Output isolation shall<br />

be not less than 16.0 dB VHF, 11.5 dB UHF.<br />

D. Four-way line splitter shall have a signal loss of not more than VHF 6.2 dB; UHF 6.7 Db.<br />

E. Splitters shall be Blonder-Tongue model MS-2U/V stock No. 3435 or MS-4U/V Stock No.<br />

3436.<br />

F. Multi-port Taps: Shall have a flat frequency response over the entire operating bandwidth of<br />

550 Mhz. Taps shall be 8 port with equal loss between all ports. The unit shall be of the<br />

hybrid design with a 75 ohm match of 24.0 dB.<br />

G. Distribution Amplifiers: Shall have an operating range of 54-550 Mhz. and provide a flat gain<br />

of 30 dB forward and 20 dB reverse with internal slope and tilt adjustment. Amplifier must be<br />

117 volt AC line powered and must have modular power supply and mother-board and be<br />

capable of modular internal equalization.<br />

2.4 EQUIPMENT AND MATERIALS:<br />

A. Agile Modulator: Blonder Tongue, AM-60-860, Qty: 1<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

TELEVISION SYSTEMS 16780-2