non-volatile memory, which is not dependent upon the presence of a<br />

battery to be retained.<br />

c. The VAV terminal manufacturer shall provide a multi-point, averaging,<br />

differential pressure sensor mounted on the inlet to each VAV box. The<br />

BAS contractor shall supply a line to low voltage transformer, of sufficient<br />

capacity, to power the controller plus all reheat valves and/or contactors<br />

and fan circuits associated with the VAV terminal and actuator<br />

assemblies. The BAS contractor shall provide all reheat control valves to<br />

the mechanical contractor for mounting and piping. The BAS contractor<br />

shall provide and install all wiring between the valve and controller and<br />

between the room sensor and the controller.<br />

d. Controller shall have manual positioning of the actuator and include a<br />

visual indication of the position of the actuator.<br />

e. Controller shall have LED indication of transmit/receive communications<br />

performance, as well as for the proper/improper operation of the<br />

controller itself.<br />

f. Controller shall support a peer to peer network using two wire type<br />

independent topologies without regard for the polarity of wiring. Wiring of<br />

communications shall support "Ts", "Stars", "Active Ts", "Active Stars"<br />

and "Distributed Stars" and other configurations without the use of<br />

termination resistors.<br />

g. Controller shall have zone temperature control of +/- 1 Deg F from<br />

setpoint.<br />

h. Controller shall have internal differential pressure transducer for<br />

pressure independent applications with an accuracy of ~ 5%.<br />

Controller shall be powered by a 24 VAC power source and shall comply<br />

with Class 2 wiring requirements.<br />

j. Controller shall be rated for service from 32 Deg. F to 131 Deg. F.<br />

k. Controller shall meet or exceed IEC 801.5 and ANSI C62.41 (IEEE-587,<br />

Category A & B) for surge immunity, IEC 801.4 for transient compliance<br />

and IEC 801.2 for electrostatic discharge. Where<br />

mounted in supply or return air plenums, the MNL-V2 enclosures shall<br />

comply with the requirements of UL 94-5V.<br />

l. MNL-V2 Input/Output.<br />

1) Self-calibrating Velocity Pressure Input (0-2" WC). The velocity<br />

pressure transducer shall be a continuously self-calibrating unit,<br />

which determines the zero velocity pressure point, by equalizing<br />

the pressure across the sensing element, every 10-15 seconds.<br />

2) Room Temperature Input.<br />

3) Occupancy Override Input.<br />

4) VAV Box Damper Output: Unless otherwise specified, the<br />

controller shall provide a minimum 6 N-m/53 Ib./inch integral<br />

electric actuator, having a 90 degree stroke rotation in a time of<br />

3 minutes maximum.<br />

5) Occupancy or Status Input.<br />

6) 0-100% Position Indication of Primary Damper Actuator, to be<br />

direct feedback from damper actuator.<br />

7) Room Setpoint Input.<br />

8) Auxiliary Temperature Input.<br />

9) Discharge air temperature sensor, located downstream of<br />

reheat coil.<br />

m. In addition to the inputs and output points described above, MNL<br />

controllers for fan assisted and/or reheat configurations, provide the<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION<br />

AUTOMATIC TEMPERATURE CONTROLS 15900-7