7. Lightning protection shall be a standard feature of the fire alarm control<br />

panel and shall be incorporated in the power supply circuit, common<br />

control circuits, signal circuits, and telephone line circuit.<br />

8. Individual circuit breakers shall be provided for the following: smoke<br />

detector power, main power supply, signal circuit #1, signal circuit #2,<br />

battery standby power, and auxiliary output.<br />

9. The fire alarm control panel shall be of dead-front construction. One key<br />

shall allow access to all electronics or to the dead-front access to the<br />

operator functions.<br />

10. Opening the main door shall expose all components for inspection or<br />

adjustment without further dismantling of the cabinet, control unit, or<br />

wiring.<br />

11. It shall be possible to check and adjust the sensitivity of all analog<br />

devices from the main fire alarm panel.<br />

M. The fire alarm control panel shall have batteries capable of powering the system for (24)<br />

hours in standby condition and (5) minutes in alarm.<br />

N. There shall be no special tools required for the programming of devices. A standard slot<br />

head screwdriver only.<br />

2.4 REMOTE OPERATING PANEL: NGA<br />

A. Remote Operating Panel (Provide color as selected by Architect)<br />

B. The fire alarm control panel shall contain a LCD Graphic Annunciator touch-screen and<br />

permit the user to perform all necessary functions including but not limited to the following:<br />

2.5 PRINTER:<br />

1. Up to 512 user-defined messages<br />

2. 77 character length messages<br />

3. Different font and color for each message<br />

4. Alarm/Trouble Acknowledge.<br />

5. Alarm Silence<br />

6. Reset<br />

7. Lamp Test<br />

8. Control of Initiating Devices (on/off)<br />

9. Control of output modules (on/off)<br />

10. Change sensitivity of devices<br />

11. Change time<br />

12. Walk test<br />

13. Check system on battery voltage and current<br />

A. The fire alarm control panel shall report all status changes to an 80 column wide carriage<br />

printer using 8.5"x11 standard printer paper. The printer shall be supervised by the control<br />

panel. In the event of a power outage, the control panel shall be capable of storing and<br />

printing out the last 4100 events, including event during the power outage.<br />

B. The panel shall report a supervisory signal to the printer every 8 hours.<br />

2.6 MONITOR MODULE: AMM-4F:<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

FIRE ALARM SYSTEMS 16723-6