SECTION 16470 - PANELBOARDS<br />

PART 1 - GENERAL<br />

1.1 WORK INCLUDED:<br />

A. Provide all branch circuit panelboards as herein specified and shown on the drawings.<br />

1.2 SUBMITTALS:<br />

A. Submit complete and descriptive shop drawings indicating dimensions and compliance with<br />

the specifications herein. Submit in accordance with Section 01300.<br />

PART 2 - PRODUCTS<br />

2.1 ACCEPTABLE MANUFACTURERS:<br />

A. Square D, Siemens, General Electric, Cutler-Hammer/Westinghouse<br />

B. Requests for substitution of other products will be considered if submitted in accordance with<br />

Section 01630.<br />

2.2 EQUIPMENT:<br />

A. Panels shall be factory pre-assembled using bolt-on circuit breakers, equivalent to Square D<br />

NQOD series. Separate feeder lugs shall be provided for each feeder conductor.<br />

B. Breakers in branch panelboards shall be not less than 3/4 inch on centers. Each breaker<br />

shall be securely fastened to prevent movement and trims shall fit neatly and tightly to the<br />

breaker assembly. Two and three pole breakers shall be single breaker assembly rather than<br />

two or three single pole breakers with the handles tied together externally.<br />

C. Panel finish shall be a flat, light gray finish suitable for painting over or being left with factory<br />

finish. Flush mounted panels in finished walls shall be painted to match wall, paint and paint<br />

preparation to be as specified by Architect. Panel covers to be painted off wall, then installed<br />

over painted wall surface. Trims to be separately packed and protected from scratching and<br />

marring. Refer to labeling requirements in 16050 Basic Materials and Methods.<br />

D. Panelboard trims to have concealed trim screws and door hinges, and a flush stainless steel<br />

cylinder lock with catch and coil spring loaded door pull equivalent to Square D "Mono-Flat".<br />

All panels shall be keyed alike.<br />

E. Where grounding conductors are shown or specified, provide each panel and distribution<br />

center with grounding bus to which the grounding conductors shall be connected, each<br />

having its own terminal or lug.<br />

F. Where Isolated Grounding (IG) conductors are shown or specified, provide each panel and<br />

distribution center with an Isolated Grounding bus to which the IG conductors shall be<br />

connected, each having its own terminal or lug. The IG grounding system shall be fully<br />

separated and insulated from the IG receptacle to the System Grounding Electrode. Provide<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

PANELBOARDS 16470-1