a. When tested in accordance with ASTM E283, the air infiltration at 6.24 psf<br />

must not exceed 0.06 cfm per square foot of wall area.<br />

2. Static Water Infiltration:<br />

a. When tested at a differential static pressure of 15.0 psf for 15 minutes, in<br />

accordance with ASTM E331, any uncontrolled water passing into the roomside<br />

beyond the interior barrier of the wall system shall not be permitted. The<br />

panel system shall be designed to provide controlled drainage to the exterior<br />

face of the wall for any leakage of water occurring at joints and/or<br />

condensation taking place within the wall system.<br />

3. Dynamic Water Infiltration:<br />

a. Shall be tested in accordance with AAMA 501 with a slipstream velocity,<br />

creating a pressure on the wall equivalent to 15.0 psf with a water spray rate of<br />

5 gallons per hour per square foot for 15 minutes with no uncontrolled water<br />

leakage to the room-side.<br />

4. Structural Performance:<br />

a. Shall be tested in accordance with ASTM E330 at design pressure. Deflection<br />

limitations are listed previously. After initial test, test at 150% of design<br />

pressure; no permanent deformation exceeding L/1000 or failure to structural<br />

members allowed.<br />

5. Seismic Racking:<br />

a. There shall be no failure or deterioration of the system when the unit is laterally<br />

racked to 3/4” in both directions and repeated for three (3) cycles. System<br />

must pass the static water requirements as described in the Static Water<br />

Infiltration Section 1.05 A 2, following the seismic racking.<br />

C. Bond Integrity Test: In accordance with ASTM D 1781-76 for bond integrity, simulating<br />

resistance to delaminating (No other test procedure is acceptable):<br />

1. Peel strength: 22.5 in lb/in (min)<br />

D. Fire Performance:<br />

1. ASTM E84-79 - Maximum value flame spread 0, smoke developed 0.<br />

2. UBC 17-5 - No flame spread along interior face or penetration through the wall<br />

assembly.<br />

3. ASTM 162 - No surface flaming.<br />

1.06 PRODUCT HANDLING<br />

A. After acceptance of panels on a given elevation, protection shall be the responsibility of the<br />

General Contractor.<br />

PART 2 – PRODUCTS<br />

2.01 COMPOSITE PANEL SYSTEM<br />

A. Fabricator: ESC Alucobond ! Architectural Wall System manufactured by Elward Systems<br />

Corporation of Lakewood, Colorado. (800) 933-5339 or (303) 239-6303.<br />

B. Panel System: The panel system shall consist of Alucobond ! manufactured by Alcan<br />

Composites USA Inc., Benton, Kentucky, and a system of custom aluminum extrusions as<br />

specified herein. The panel shall conform to all of the following,<br />

1. Perimeter Extrusions: Extruded aluminum with integral weather-stripping as detailed<br />

on drawings, so as to provide the following essential features,<br />

________________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION MARCH 2, 2009<br />

COMPOSITE PANELS 07430 - 4