I. Floor boxes which contain voice and data cable often are shown with an empty conduit<br />

running up a wall and stubbing into the ceiling. Where no conduit is shown, stub a 1" conduit<br />

out the bottom of the low voltage section of the box and into the ceiling space of the floor<br />

below.<br />

PART 3 - EXECUTION<br />

3.1 GENERAL INSTALLATION METHODS:<br />

A. All items, articles, materials, and equipment specified under this Division shall be installed per<br />

the manufacturer’s installation instructions. Where the manufacturer’s instructions are in<br />

conflict with the directions provided elsewhere in this Contract, the Engineer shall be notified<br />

prior to beginning rough-in.<br />

B. Cutting or notching shall be kept to an absolute minimum and done when, and in a method<br />

approved by the Architect. Patch and correct finished surfaces damaged by electrical work.<br />

C. Relays, panels, cabinets and equipment shall be level and plumb and installed parallel with<br />

structural building lines. All equipment and enclosures shall fit neatly without gaps, openings,<br />

or distortions. Provide approved devices for closing all unused openings.<br />

D. Arrange circuit wiring as shown on the Drawings and do not alter or combine runs or<br />

homeruns without the specific approval of the Architect. Feeder runs shall not be recombined<br />

or altered.<br />

E. Contactors, transformers, starters and similar noise producing devices shall not be placed on<br />

walls which are common to occupied space.<br />

F. Ballasts, contactors, starters, transformers and like equipment which are found to be<br />

noticeably noisier than other similar equipment on the project will be deemed defective and<br />

shall be replaced.<br />

G. In general, the mounting heights shall be as noted on the Drawings, or as listed below, the<br />

Architectural Interior Elevations and drawing notes taking precedence. Where no heights are<br />

indicated, request clarification from the Architect. Consult the Architectural, Mechanical and<br />

Structural drawings to avoid conflicts prior to roughing-in and for exact locations. All<br />

dimensions are to the center of the device unless otherwise noted. Lighting dimensions are<br />

to the bottom of suspended fixtures and center of wall mounted fixtures unless otherwise<br />

noted.<br />

Light Switches 45 inches<br />

Convenience Receptacles 18 inches<br />

Panelboard top 72 inches<br />

Fire Alarm Signals 96 inches to top (but at least 6" below ceiling)<br />

Fire Call Stations 45 inches<br />

Data/Telephone Outlets 18 inches<br />

Receptacles and Outlets 8 inches above counter or 3<br />

Over Counters inches above backsplash, whichever is greater.<br />

H. Where raceways penetrate floors, ceilings, ducts, chases, and fire walls, provide fire stopping<br />

to maintain integrity of the fire assembly. Firestopping method shall be approved by the<br />

Code Authority having jurisdiction.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

BASIC ELECTRICAL MATERIALS AND METHODS 16050-5