SECTION 09650 - RESILIENT FLOORING<br />

PART 1 - GENERAL<br />

1.01 SUMMARY<br />

A Section includes resilient flooring, base and accessories.<br />

B. Related Sections:<br />

1. Division 9 Section “Tile” for transition strips at floor tile.<br />

2. Division 9 Section “Carpet” for carpet base.<br />

2. Division 12 Section “Entrance Mats” for transition strips at entrance mats.<br />

C. Related Documents: Drawings and general provisions of Contract, including General and<br />

Supplementary Conditions and Division 1 <strong>Specification</strong> sections, apply to work of this section.<br />

1.02 SUBMITTALS<br />

A. Product Data: Submit manufacturer’s technical data for each type of resilient flooring and<br />

accessory.<br />

B. Samples:<br />

1. Samples for Verification Purposes: Submit actual sections of resilient flooring,<br />

including accessories for each type of resilient flooring, and base required.<br />

C. Certification for Fire Test Performance: Submit certification from an independent testing<br />

laboratory acceptable to authorities having jurisdiction that resilient flooring complies with fire<br />

test performance requirements.<br />

D. Maintenance Instructions: Submit 2 copies of manufacturers recommended maintenance<br />

practices for each type of resilient flooring and accessory required.<br />

1.03 QUALITY ASSURANCE<br />

A. Manufacturer: Provide each type of resilient flooring and accessories as produced by a single<br />

manufacturer, including recommended primers, adhesives, sealants, and leveling compounds.<br />

B. Fire Test Performance: Provide resilient flooring which complies with the following fire test<br />

performance criteria as determined by an independent testing laboratory acceptable to<br />

authorities having jurisdiction.<br />

1. Flame Spread: Not more than 75 per ASTM E 84.<br />

2. Smoke Developed: Not more than 450 per ASTM E 84.<br />

3. Smoke Density: Not more than 450 per ASTM E 662.<br />

C. Installer’s Qualifications: Engage Installer who is certified in writing by resilient flooring<br />

manufacturer as qualified for installation of sheet vinyl employing heat welded seams.<br />

1.04 PROJECT CONDITIONS<br />

A. Maintain minimum temperature of 65 deg. F (18 deg. C) in spaces to receive resilient flooring<br />

for at least 48 hours prior to installation, during installation, and for not less than 48 hours after<br />

installation. Store resilient flooring materials in spaces where they will be installed for at least<br />

48 hours before beginning installation. Subsequently, maintain minimum temperature of 55<br />

deg. F (13 deg. C) in areas where work is completed.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION MARCH 2, 2009<br />

RESILIENT FLOORING 09650 - 1