Mode of Operation<br />

Boiler shall include integral factory wired operating controls to control all operation and energy input of the boiler.<br />

The controller shall have the ability to vary boiler input throughout its full range to maximize the condensing<br />

capability of the boiler without header temperature swings.<br />

The boiler will operate to vary header temperature setpoint linearly as an externally applied 4-20 ma signal is<br />

supplied. Unit shall operate with an Inverse Efficiency Curve, with known Part Load Value Efficiencies.<br />

Maximum efficiency shall be achieved at minimum firing input. Main Header outlet temperature shall not be<br />

more than +/-2F from setpoint at any point of operation. The boiler shall have LCD display for monitoring of all<br />

sensors and interlocks.<br />

Warranty<br />

The pressure vessel of boiler shall carry an unconditional, non-prorated 10 year warranty against leakage due to<br />

defective materials or workmanship. The heat exchanger tubes/combustion chamber assembly shall be<br />

warranted against failure due to thermal stress failure or condensate corrosion for a prorated five year period. A<br />

Warranty Certificate must be issued to the owner from the manufacturer and a copy of warranty be submitted for<br />

engineers approval.<br />

Field Services<br />

Contractor shall provide the services of a local factory authorized representative to supervise all phases of<br />

equipment startup. A letter of compliance with all factory recommendations and installation instructions shall be<br />

submitted to the engineer with operation and maintenance instructions.<br />

Boiler shall be Aerco or Fulton<br />

AIR COOLED CHILLER:<br />

SYSTEM DESCRIPTION<br />

Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans<br />

QUALITY ASSURANCE<br />

A. Unit shall be rated in accordance with ARI Standard 550/590, latest revision (U.S.A.).<br />

B. Unit construction shall comply with ASHRAE 15 Safety Code, UL 1995, and ASME applicable codes<br />

(U.S.A. codes).<br />

C. Unit shall be manufactured in a facility registered to ISO 9001:2000 Manufacturing Quality Standard.<br />

D. Unit shall be full load run tested at the factory.<br />

DELIVERY, STORAGE AND HANDLING<br />

A. Unit shall be stored and handled per unit manufacturer's recommendations.<br />

EQUIPMENT<br />

A. General:<br />

Factory assembled, single-piece or factory-matched duplex chassis, air-cooled liquid chiller.<br />

Contained within the unit cabinet shall be all factory wiring, piping, controls and refrigerant charge.<br />

B. Unit Cabinet:<br />

____________________________________________________________________________________________________________________________________________________________________________________<br />

____<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

HEATING-COOLING 15700-2