1. Submit documentation, including illustrations, from a qualified testing and inspecting<br />

agency that is applicable to each through-penetration firestop configuration for<br />

construction and penetrating items.<br />

1.05 QUALITY ASSURANCE<br />

A. Fire-Test-Response Characteristics: Provide firestopping that complies with the following<br />

requirements and those specified under the "System Performance Requirements" article:<br />

1. Firestopping tests are performed by a qualified testing and inspecting agency. A<br />

qualified testing and inspecting agency is UL, Warnock Hersey, or another agency<br />

performing testing and follow-up inspection services for firestop systems that is<br />

acceptable to authorities having jurisdiction.<br />

a. Through-penetration firestop system products bear classification marking of<br />

qualified testing and inspecting agency.<br />

b. Fire-Resistance Ratings of Joint Sealants: As indicated by reference to<br />

design designations listed by UL in their "Fire Resistance Directory" or by<br />

another qualified testing and inspecting agency,<br />

c. Joint sealants, including backing materials, bear classification marking of<br />

qualified testing and inspection agency.<br />

B. Single-Source Responsibility: Obtain through-penetration firestop systems for each kind of<br />

penetration and construction condition indicated from a single manufacturer.<br />

C. Provide firestopping products containing no detectable asbestos as determined by the<br />

method specified in 40 CFR Part 763, Subpart F, Appendix A, Section 1, "Polarized Light<br />

Microscopy."<br />

D. Coordinating Work: Coordinate construction of openings and penetrating items to ensure that<br />

designated through-penetration firestop systems are installed per specified requirements.<br />

E. Installer shall be certified by manufacturer's representative. Manufacturer's representative<br />

(not distributor or agent) shall be on the project site during initial installation to train contractor<br />

on proper firestop installation procedures.<br />

1.06 DELIVERY, STORAGE, AND HANDLING<br />

A. Deliver firestopping products to Project site in original, unopened containers or<br />

packages with intact and legible manufacturers' labels identifying product and<br />

manufacturer; date of manufacture; lot number; shelf life, if applicable; qualified<br />

testing and inspecting agency's classification marking applicable to Project; curing<br />

time; and mixing instructions far multicomponent materials.<br />

B. Store and handle firestopping materials to prevent their deterioration or damage due<br />

to moisture, temperature changes, contaminants, or other causes.<br />

1.07 PROJECT CONDITIONS<br />

A. Environmental Conditions: Do not install firestopping when ambient or substrate<br />

temperatures are outside limits permitted by firestopping manufacturers or when<br />

substrates are wet due to rain, frost, condensation, or other causes.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION MARCH 2, 2009<br />

FIRESTOPPING 07270-2