F. Shall have a standard 30 element Fresnel lens with 15 layers horizontally and 4 layers<br />

vertically, a 14 element Long Range Fresnel lens with 9 layers horizontally and 4 layers<br />

vertically, or an Aisle Way Fresnel lens with 14 layers horizontally and 9 layers vertically.<br />

G. Shall cover up to 1200 square feet with the Standard Lens, up to 90 linear feet with the Long<br />

Range Lens, and up to 120 linear feet with the Aisle Way Lens for walking motion when<br />

mounted at a ceiling height of 12 feet.<br />

H. Shall operate on 24 VDC, current draw of 19 Ma.<br />

I. Watt Stopper Model CX-100<br />

2.5 CEILING MOUNT ULTRASONIC TYPE (For Restrooms, Open Office Areas up to 1000 square<br />

feet)<br />

A. Shall be omni-directional with volumetric coverage of 360 degrees and up to 1000 square<br />

feet of walking motion.<br />

B. Shall have a multi-direction transmitter with temperature and humidity resistant, minimum 32<br />

kHz tuned ultrasonic receivers. Ultrasonic receivers shall be temperature and humidity<br />

resistant with less than a 6dB shift in the humidify range of 10% to 90% and less than a 10dB<br />

shift in the temperature range of -20 to 60 degrees C.<br />

C. Sensors of varying frequencies shall not be allowed so as to prevent sensors from interfering<br />

with each other and to ensure compatibility in the event more sensors are added or units are<br />

replaced.<br />

D. Shall be furnished with a convenient shunt provision which will enable a by-pass in the event<br />

of failure. This by-pass provision pin shall remain in the sensor and be visible from the floor<br />

as a constant reminder that the automatic function has been by-passed.<br />

E. Shall have user-adjustable sensitivity setting and time delay setting from 15 seconds to 15<br />

minutes.<br />

F. Shall operate on 24 VDC, current draw of 15 mA.<br />

G. Watt Stopper Model W-1000A<br />

2.6 CEILING MOUNT DUAL-TECHNOLOGY TYPE (For Rooms up to 1200 SF)<br />

Low Profile, ceiling mount, 360 degree coverage: Watt Stopper Model DT-300<br />

Adjustable arm, wall mount, 180 degree coverage: WattStopper Model DT-200<br />

A. The Occupancy Sensors shall be capable of detecting presence in the floor area to be<br />

controlled, by detecting doppler shifts in transmitted ultrasound and passive infrared heat<br />

changes (dual technology). Sensors that utilize microphonics are not approved.<br />

B. Upon entering a space, motion from both technologies must be sensed before lighting will be<br />

turned on. After this has occurred, detection in either technology will hold lighting on for the<br />

set time period. Sensors will have a retrigger time delay where only one motion is necessary<br />

to turn on the lights within 5 seconds after turning off.<br />

C. Ultrasonic sensors will be volumetric in coverage. Up to 10 different passive infrared patterns<br />

will be available by lens selection. Detection shall be maintained when a person of average<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

OCCUPANCY SENSED LIGHTING CONTROL 16550-3