devices.<br />

4. Panel Wiring: Run all wiring within enclosed distribution gutters (similar to<br />

Panduit). all wiring entering or leaving the panel shall terminate on numbered<br />

terminal strips. All wiring entering or leaving the panel shall be tagged with a<br />

permanent, identifying tag. All wire and tube identification numbers shall be<br />

designated on the control drawings. All wiring shall be color coded and the color<br />

shall not be changed between the terminal strip and the end destination of that<br />

wire.<br />

PART 4- SEQUENCE OF OPERATION<br />

4.1 GENERAL OPERATION<br />

A. Control Programs: The control programs to achieve the sequence of operation shall reside<br />

in the field controller. These controllers shall be capable of standalone operation, such that<br />

if communication with the network level controller is lost or disrupted, the sequence of<br />

operation will continue to operate. Global functions such as Scheduling, Optimal<br />

Start/Stop, and Outside Air Temperature Reset may reside on the Global Controller.<br />

B. Optimal Start/Stop is incorporated into the District system-wide energy management<br />

program. Any time a school experiences and school wide change of state (i.e. unoccupiedoccupied<br />

or power-up after loss of electrical power), the EMS shall initiate a school wide<br />

optimal start-up procedure so as to minimize the electrical demand based on a 15-minute<br />

sliding window.<br />

C. Human Machine Interface (HMI): The HMI shall be a PC based graphical package. User's<br />

privileges determine whether setpoints and parameters can be modified or outputs<br />

manually overridden.<br />

1. This graphical package shall contain graphical representations of the mechanical<br />

equipment.<br />

2. The graphics shall display all the digital and analog points as listed in the points<br />

listed for each mechanical system.<br />

3. Digital output points shall have the capability to be manually overridden on and off<br />

from the HMI. These overrides may be timed, until or forever. Manual overrides<br />

cannot override any safety conditions.<br />

4. Analog output points shall have the capability to be manually overridden on and<br />

off from the HMI. These overrides may be timed, until or forever. Manual overrides<br />

cannot override any safety conditions.<br />

5. All setpoints, parameters and calculated values shall be displayed and adjustable<br />

from the HMI.<br />

6. All setpoints and parameters defined as (adjustable) shall be adjustable from the<br />

HMI.<br />

4.2 VAV WITH REHEAT<br />

A. Each variable air volume box consists of a room sensor, a supply damper with an over<br />

the shaft Direct Digital Controller, modulating integral damper motor with quick release,<br />

integral differential pressure sensor, Hot Water Reheat Coil, and a Flo-Cross 2 X 12<br />

points averaging and signal amplifying air flow sensor. The temperature control shall<br />

utilize Proportional, Integral and Derivative (PID) algorithms. Each VAV box shall include<br />

maximum and minimum (cooling and heating) flow settings (CFM), Morning Warm-<br />

Up/Cool-Down, Energy Consumption, and Room Temperature Control. The VAV box<br />

shall be controlled through the BAS as follows:<br />

1. Unoccupied Mode<br />

a. When the central air handling unit is off, the BAS shall command the<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION<br />

AUTOMATIC TEMPERATURE CONTROLS 15900-10