AIR SEPARATORS:<br />

Type: Provide air separators of tangential type constructed of steel and tested and stamped in accordance with<br />

section 8 of the ASME Code for a working pressure of 125 psig.<br />

Provide separators on hydronic systems capable of separating not less than 80 percent of the entrained air on<br />

the first passage of water and not less than 30 percent of residual air on each subsequent passage through the<br />

separator.<br />

Provide flanged inlet and outlet connections, 3/4-inch diameter valve drain connection and 1-inch diameter top<br />

air eliminator connection.<br />

Provide 1-inch diameter pipe from the top air eliminator point to a 5 gallon, steel, ASME stamped 125 pound<br />

working pressure air receiver vessel with automatic float vent.<br />

Provide 1-inch diameter globe valve between the air separator and the air receiver.<br />

EXPANSION TANKS:<br />

Furnish and install pre-pressurized diaphragm-type expansion tanks of sizes indicated on the drawings.<br />

Construct tanks of steel in accordance with section 8 of the ASME Code for a working pressure of 125 psig.<br />

Test and stamp tanks for the working pressure.<br />

Support tanks on 2-inch diameter steel pipe legs with cross bracing and floor plates or suspend on steel saddles<br />

with all-thread rod anchored to the structure.<br />

The tanks shall be the product of a manufacturer who certifies that his tanks have been a standard production<br />

model for five years prior to opening bids and warrants the diaphragm material unconditionally, against failure or<br />

leakage for a period of five years from the date of project acceptance.<br />

CHILLED & HOT WATER COILS:<br />

Furnish and install the cooling and heating coils of capacities as shown and specified on the drawings.<br />

Coils shall be of the extended surface type, fabricated of copper or brass tubing not less than 5/8” diameter with<br />

.035” thick walls and plate-type fins of copper or aluminum extending at right angles to the centerline of the<br />

tubes. Pressure parts of the coils shall be constructed and tested for a working pressure of not less than 200<br />

psig.<br />

Each coil section shall be mounted in a die-formed, 16 gauge, zinc-coated steel casing with mounting flanges.<br />

All coils shall have inlet, outlet, vent and drain connections for each section and shall have all connections at the<br />

same end.<br />

Coils shall be York, Dunham-Bush, Bohn, AAF, Carrier, Trane, or Thermal.<br />

____________________________________________________________________________________________________________________________________________________________________________________<br />

____<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

HEATING-COOLING 15700-20