SECTION 16478 – TRANSIENT VOLTAGE SURGE SUPPRESSORS<br />

PART 1 - GENERAL<br />

1.1 WORK INCLUDED:<br />

A. Furnish all labor, materials, equipment and services necessary for and incidental to the<br />

installation of the Transient Voltage Surge Suppression (TVSS) System components at<br />

locations shown on the plans.<br />

1.2 QUALITY ASSURANCE:<br />

A. The TVSS shall be UL Listed as a Transient Voltage Surge Suppressor, category C, UL 1449<br />

Second Edition (including Sections 34 and 37.3, effective February 7, 2007). All UL 1449 test<br />

data shall be provided with submittal.<br />

B. The TVSS shall bear suppressed voltage rating issued by UL, and the units shall be tested in<br />

accordance with ANSI/IEEE C62.41-1991, Category C, 20kV/10kA, 8x20 uS and 1.2x50 uS<br />

Combination Waveform and .5uS - 100kHz Ring Wave with a minimum of 10 sequential<br />

impulses delivered directly into the TVSS at a maximum of sixty second intervals for each<br />

waveform.<br />

C. Manufacturers Qualifications: Only firms regularly engaged in the manufacture of TVSS<br />

products for category C (ANSI/IEEE C62.41), and whose products have been providing<br />

satisfactory service for not less than five years, shall be considered. Manufacturer<br />

qualifications shall be provided as part of the submittal.<br />

D. The TVSS must be capable of surviving 1000 sequential surges without failure, using IEEE<br />

test procedures established in C62.45.<br />

E. The TVSS device must have MOV surge devices, installed with full rating indicated between<br />

Phase to Neutral, Phase to Ground, and Neutral to Ground, and be capable of handling a<br />

minimum surge current as follows:<br />

Distribution and/or service panels:<br />

Per Mode:<br />

Branch panels:<br />

Line to Neutral 150,000 amps<br />

Line to Ground 150,000 amps<br />

Neutral to Ground 150,000 amps<br />

Per Phase: 300,000 amps<br />

Per Mode:<br />

Line to Neutral 40,000 amps<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

TRANSIENT VOLTAGE SURGE SUPPRESSORS 16478-1