PART 3 - EXECUTION<br />

3.1 INSTALLATION<br />

TR's=50% 5 foot patch cables part numbers<br />

5 foot – MX6-8T-05-B02<br />

TR's=50% 7 foot patch cables part numbers<br />

7 foot – MX6-8T-07-B02<br />

NO CABLE WILL BE ALLOWED TO BE INSTALLED WITHOUT HAVING ADEQUATE SUPPORTS<br />

EVERY 3 FEET OF THE ENTIRE SPAN OF THE CABLE.<br />

FREE SPANNING OF CABLE WILL NOT BE ALLOWED IN ANY SPAN LONGER THAN 36<br />

INCHES FROM CABLE TRAY OR CONDUIT.<br />

CABLE BASKET TRAY IS TO BE INSTALLED BY DIVISION 26000 CONTRACTORS. THIS<br />

SHOULD BE INSTALLED BELOW ALL MECHANICAL PATHWAYS FOR ACCESS DURING<br />

INSTALLATION, AND FOR FUTURE CABLING NEEDS.<br />

A. Penetrations through floor and fire-rated walls shall utilize intermediate metallic conduit (IMC)<br />

or galvanized rigid conduit (GRC) sleeves, and shall be fire stopped after installation and<br />

testing, utilizing a fire stopping assembly approved for that application. To be completed by<br />

division 16000 contractors.<br />

B. Install conduits for station cabling to the nearest communications closet, unless otherwise<br />

noted. To be completed by division 16000 contractors.<br />

*NO CONDUIT SHALL EXCEED 40% FILL AS ACCORDING TO SIEMON INSTALLATION<br />

SPECIFICATIONS REGARDLESS OF CONDUIT LENGTH.<br />

ACCORDING TO SIEMONS REFERENCE GUIDE FOR CONDUIT FILL, SEE GUIDE<br />

BELOW:<br />

1 ! - INCH CONDUIT CAN HAVE NO MORE THAN 6 CABLES WITHIN<br />

1 - INCH CONDUIT CAN HAVE NO MORE THAN 3 CABLES WITHIN<br />

" - INCH CONDUIT CAN HAVE NO MORE THAN 2 CABLES WITHIN<br />

**NO CABLE RUN SHALL EXCEED 90 METERS/280 FEET FROM STATION LOCATION<br />

TO NEAREST IDF, INCLUDING SERVICE LOOP AS PER SPECS AND PATCH CABLES<br />

ON TERMINATION END AND MDF/IDF UPLINK,, AND SHOULD NOT EXCEED A TOTAL<br />

OF 180 DEGREE BEND RADIUS ( Except as approved in ANSI/TIA/EIA 569 standards)IN<br />

THE ENTIRE SPAN OF THE RUN.<br />

C. A minimum of (1) 1 1/4 inch conduit will be used for all “B” LOCATIONS, L4 LOCATIONS OR<br />

ANY CABLE COUNTS LARGER THAN 4 CABLES IN ONE LOCATION. ALL conduits will be<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

TELEPHONE AND DATA DISTRIBUTION 17000-10