Starters shall be two-speed type or explosion-proof type where required.<br />

Provide a heater index bound in the mechanical section of the O & M manuals for all starters furnished on the<br />

project.<br />

MOTORS:<br />

Motors shall be furnished and installed under the applicable Mechanical Sections of the <strong>Specification</strong>s.<br />

Each motor shall be provided with a nameplate for the electrical characteristics shown on the Drawings or as<br />

otherwise noted.<br />

Motors shall be constructed and rated to deliver full nameplate capacity at the project altitude.<br />

Horsepower shall be at least equal to that shown on the drawings. Where equipment is submitted and approved<br />

for the installation which requires larger motor sizes than shown, the wire and starter sizes shall be increased<br />

and means provided for operation and control suitable for the larger motors with no increase in cost to the<br />

Owner.<br />

Unless otherwise specified, or required for controller sequencing, all motors over 5 HP shall be premium<br />

efficiency type, and all fractional HP single phase motors 1/2 HP & under shall be permanent split capacitor<br />

(PSC) type.<br />

Premium efficiency motors shall be based on CEE premium efficiency criteria for OPD motors at 1800 RPM.<br />

HORSEPOWER NEMA PREMIUM EFFICIENCY<br />

5 89.5%<br />

7.5 91.0%<br />

10 91.7%<br />

15 93.0%<br />

20 93.0%<br />

25 93.6%<br />

30 94.1%<br />

40 94.1%<br />

50 94.5%<br />

Motors for V-belt drives shall be provided with cast iron or steel base, with slide rail and adjustable screw device<br />

and shall be isolated by rubber-in-shear devices.<br />

Motors shall have sufficient capacity to start and operate the machine it drives without exceeding the motor<br />

nameplate rating at the speed specified or at any speed and load which may be obtained by the drive actually<br />

furnished.<br />

______________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDTION March 2, 2009<br />

BASIC MATERIALS & METHODS 15050-16